| Plan Review Notes For Permit 09060290 |
| Permit Number |
09060290 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-09-21 15:52:19 | ** TEMP FAILED, CALLED AND LEFT MESSAGE ON CONTRACTOR | | | VOICEMAIL. NEED AIC RATING OF NEW MAIN BREAKER PANEL. | | | 110.9 | | | | | | ALSO WAS GOING TO REDLINE PLANS FOR METALLIC CWP AND | | | 2ND GRND ROD PER 250.50, 250.56 | | | |
|