2009-09-21 15:52:19** TEMP FAILED, CALLED AND LEFT MESSAGE ON CONTRACTOR
 VOICEMAIL. NEED AIC RATING OF NEW MAIN BREAKER PANEL.
 110.9
  
 ALSO WAS GOING TO REDLINE PLANS FOR METALLIC CWP AND
 2ND GRND ROD PER 250.50, 250.56
  