| 2009-07-05 12:22:33 | |
| | ** DENIED PLANS REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING MINIMUM CODES ARE |
| | STATED ON PLANS AS THEY ARE RELEVANT FOR THE MINIMUM |
| | DESIGNS. |
| | 2007 FBC W/ 2009 SUPPLEMENTS |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | |
| | 2) NOTE: THE ENGINEERING FIRM SHALL INCLUDE ALL |
| | REQUIRED INFORMATION ON TITLE BLOCKS PER FAC |
| | 61G15-23.002. PLEASE ALSO SEE THE SAME SECTION OF THE |
| | FLORIDA ADMINISTRATIVE CODE REQUIRES THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. THIS IS AN REQUIRED LICENSE |
| | NUMBER PER FLORIDA STATUTES 471.023 |
| | IF THERE ARE ANY QUESTIONS ON HOW TO PROCEED PLEASE |
| | CALL. |
| | |
| | 3) NOTE: PLEASE SEE 13-415.AB.5. PLEASE PROVIDE SPACE |
| | OF NEW WORK SHOWING NEW LIGHTING TO EXISTING. THE |
| | ADDITION OF NEW LIGHTING TO EXISTING MAY OR MAY NOT |
| | EXCEED LIGHTING LEVELS PERMITTED. |
| | PLEASE CALL TO GO OVER AS ALLOWANCES IN THE FBC AS THEY |
| | HAVE CHANGED SUBSTANTIALLY. THE LIGHTING LAYOUT ON |
| | PLANS DOES NOT SEEM TO COORDINATE WITH THE ACTUAL |
| | LOCATION FOR ALL LIGHTS. |
| | |
| | *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE |
| | PERMITS. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |