| Plan Review Notes For Permit 09060278 |
| Permit Number |
09060278 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-22 17:04:36 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE REVISE GOVERNING CODE, INCLUDING 2009 | | | SUPPLEMENTS. | | | | | | 2. INCORRECT ASCE 7 REFERENCE, SEE FBC 35. | | | | | | 3. THIS PROPERTY IS IN EXPOSURE C, PLEASE REVISE PLANS, | | | DESIGN CRITERIA, TRUSS ENGINEERING, ETC. AS NECESSARY. | | | FBC1609, ASCE7-05. | | | | | | 4. PLEASE SUBMIT TWO SETS OF ONE PRODUCT APPROVAL FOR | | | THE SHINGLES. SEVERAL DIFFERENT NOAS SUBMITTED. PLEASE | | | PROVIDE TWO COMPLETE SETS OF ONE NOA. | | | | | | 5. PLEASE CLARIFY, 25 PSF ATTIC LIVE LOAD SPECIED ON | | | PLAN, NOT INCLUDED ON TRUSS ENGINEERING, NO ATTIC | | | ACCESS, BUT THIS IS A SCISSOR TRUSS. HOW WILL YOU | | | ACCOMODATE A 25PSF LIVE LOAD IN THE LIMITED SPACE? | | | | | | 6. DESIGNER OF RECORD IS TO REVIEW THE TRUSS | | | ENGINEERING, FAC61G31. | | | | | | 7. PROVIDE A SITE PLAN WHICH SHOWS THE PROPOSED | | | IMPROVEMENT IN RELATION TO THE PROPERTY LINE AND | | | EXISTING STRUCTURE, FBC R301. | | | | | | |
|