| Plan Review Notes For Permit 09060251 |
| Permit Number |
09060251 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2009-09-25 20:26:40 | ** PROVISO ** | | | | | | 1) NOTE: PLEASE SEE 13-415.AB.5, 13-415.B.1 AND | | | APPENDIX B FOR LIGHTING PERFORMANCE CALCULATIONS. | | | PLANS NEED TO INDICATE THE TOTAL ALLOWED WATTAGE AND | | | THE TOTAL DESIGN. BASED ON THE AMOUNT SHOWN ON PLANS | | | THE DESIGN AND ALLOWABLE IS NOT SHOWN AS NEEDED. | | | PLEASE CALL TO GO OVER. | | | | | | ** SEPARATE PERMITS FOR LOW VOLTAGE SYSTEMS INCLUDING | | | PLANS. | | | ** SEPARATE PERMIT AND PLAN LAYOUT FOR ANY FIRE ALARM | | | DEVICE RELOCATIONS OR INSTALLATIONS. ( PLEASE BE SURE | | | TO SEE FBC CHAPTER 11 FOR ADA COMPLIANCE FOR ALL | | | DEVICES. 11-4.28.1, .2 AND .3. | | | | | | ** ALL OTHER CHANGES ARE REQUIRED TO BE REVISED BEFORE | | | ROUGH ALONG WITH COMMENTS ABOVE. | | | | | | ** IMPORTANT** | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|