| Date |
Text |
| 2009-09-21 14:54:29 | |
| | |
| | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: IF NEW CONTROL IS INSTALLED FOR REAR EXTERIOR |
| | LIGHT IT MUST MEET 13-415.AB.1.4. |
| | |
| | 2) NOTE: RISER DIAGRAM AND PANEL SCHEDULES INDICATE ALL |
| | EQUIPMENT AS EXISTING. HOWEVER SOME ITEMS ARE IN NEED |
| | OF MINIMUM CODE COMPLIANCE AS THEY ARE FIRE AND LIFE |
| | SAFETY HAZARDS. |
| | RISER INDICATES TAPPED CONDUCTORS FROM GUTTER TO EACH |
| | PANEL. PLEASE 240.21 AS ALL TAPPED CONDUCTORS SHALL |
| | TERMINATE IN OVER CURRENT PROTECTION. PLEASE ALSO SEE |
| | 408.36 FOR ANY LIGHTING AND APPLIANCE PANEL BOARDS. |
| | |
| | THE PANELS ARE ALL SHOWN AS 225AMP MLO. EVEN IF 225AMP |
| | MAINS WERE INSTALLED, TWO OF THE PANELS SUCH AS *A* AND |
| | *C* HAVE 3/0 CONDUCTORS TAPPED FROM GUTTER WHICH ARE |
| | NOTE RATED FOR 225AMPS. |
| | 310.16, 110.14. |
| | |
| | THE RISER ALMOST APPEARS TO INDICATE 2-POLE 225AMP |
| | BREAKERS FOR EACH, HOWEVER THIS DOES NOT SEEM POSSIBLE |
| | WHEN THE CONDUCTORS RUN TO PANELS ARE FOR 3-PHASE |
| | PANELS AND EACH OF THE PANEL SCHEDULES ALSO INDICATE |
| | THESE PANELS AS 3-PHASE. |
| | |
| | ** THERE ARE ITEMS ON THE ABOVE WHICH ARE NOT KNOWN. IN |
| | BOTH CASES 3/0 AWG IS ONLY FOR 200AMP IN COMMERCIAL |
| | INSTALLATIONS. |
| | |
| | 3) NOTE: THERE ARE LIGHT FIXTURES WHICH ARE NOTED AS |
| | 250W PAR -38 FIXTURES FOR TRACKS. PLEASE EXPAND ON |
| | LIGHTING CALCULATIONS ON THE AMOUNT OF WHICH TYPE OF |
| | FIXTURES ARE GOING TO BE INSTALLED. |
| | |
| | 4) NOTE: PLEASE SHOW WHERE LOADS IN CALCULATIONS ARE |
| | SHOWN PER 220.43 A AND B. |
| | |
| | 5) NOTE: PLEASE SEE 210.8B2 AS ALL 15/20AMP 120V |
| | RECEPTACLES IN KITCHEN ARE REQUIRED TO BE GFI/GFI |
| | PROTECTED. |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |