| 2009-07-02 14:06:49 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 PLUMBING |
| | FBC-2007 FUEL GAS |
| | FBC-2007 CHAPTER 1 ADMIN |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. SHT C-1 PROJECT DATA INDICATES FBC-2004 W/2006 |
| | AMENDMENTS. ALL APPLICATIONS FOR PERMIT SUBMITTED ON OR |
| | AFTER MARCH 1, 2009 SHALL BE DESIGNED TO THE FBC-2007 |
| | WITH 2009 SUPPLEMENTS. PLEASE CORRECT TO THE CORRECT |
| | CODE CYCLE. SECTION 110.1.2(7). |
| | |
| | 2. SHT A-1 INDICATES 3 "WHS" TO BE ADDED. THESE ARE NOT |
| | SHOWN ON OTHER SHEETS. PLEASE CLARIFY. HAND WRITTEN |
| | INFORMATION IS NOT APPROVED ON SIGNED, SEALED, DATED |
| | PLANS. A REVISION IS REQUIRED FOR NEW INFORMATION ADDED |
| | TO THE PLANS. SECTION 106.1.3. THE EXISTING SHEET A-1 |
| | WITH THE FOOD SERVICE APPROVAL STAMP CAN BE RESUBMITTED |
| | IN THE PLANS AS A REFERENCE SHEET ONLY. -- IF THE WHS'S |
| | ARE TO BE INSTALLED, THEN THE PLUMBING PLANS SHALL |
| | REFLECT THE INSTALLATION. |
| | |
| | 3. A GREASE INTERCEPTOR IS INDICATED. THE GREASE |
| | INTERCEPTOR SHALL BE APPROVED BY THE UTILITY DEPT. |
| | INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE. |
| | PLEASE CONTACT HOLLY MCGRATH, LABORATORY SUPERVISOR, |
| | (561) 822-2271, (FAX) (561) 822-2279, OR E-MAIL |
| | [email protected]. A WRITTEN DETERMINATION OR E-MAIL OF |
| | APPROVAL IS REQUIRED FOR OUR FILES. ARTICLE III SECTION |
| | 90-124(7) & SECTION 1003.2. |
| | |
| | 4. SHTS P-1 & P-2. THE JANITOR SINK SHALL DISCHARGE |
| | THROUGH THE GREASE INTERCEPTOR. SECTION 1003.1. |
| | |
| | 5. THE DISHWASHER IS PROHIBITED FROM DRAINING INTO THE |
| | GREASE LINE AND SHALL CONNECT TO THE SANITARY LINE. |
| | ARTICLE III SECTION 90-124(7)(B). |
| | |
| | 6. IF THERE IS A FOOD WASTE GRINDER CONNECTING TO THE |
| | GREASE INTERCEPTOR, THEN A SOLIDS INTERCEPTOR IS |
| | REQUIRED. SECTION 1003.3.2. |
| | |
| | 7. GREASE INTERCEPTORS SHALL BE EQUIPPED WITH DEVICES |
| | TO CONTROL THE RATE OF WATER FLOW SO THAT THE WATER |
| | FLOW DOES NOT EXCEED THE RATED FLOW. SECTION |
| | 1003.3.4.2. |
| | |
| | 8. INFORMATIONAL: A SEPARATE GREASE INTERCEPTOR PERMIT |
| | IS REQUIRED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |