Plan Review Notes
Plan Review Notes For Permit 09060251
Permit Number 09060251
Review Stop P
Sequence Number 1
Notes
Date Text
2009-07-02 14:06:49DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 FUEL GAS
 FBC-2007 CHAPTER 1 ADMIN
 CITY WPB MUNICIPAL CODE
  
 1. SHT C-1 PROJECT DATA INDICATES FBC-2004 W/2006
 AMENDMENTS. ALL APPLICATIONS FOR PERMIT SUBMITTED ON OR
 AFTER MARCH 1, 2009 SHALL BE DESIGNED TO THE FBC-2007
 WITH 2009 SUPPLEMENTS. PLEASE CORRECT TO THE CORRECT
 CODE CYCLE. SECTION 110.1.2(7).
  
 2. SHT A-1 INDICATES 3 "WHS" TO BE ADDED. THESE ARE NOT
 SHOWN ON OTHER SHEETS. PLEASE CLARIFY. HAND WRITTEN
 INFORMATION IS NOT APPROVED ON SIGNED, SEALED, DATED
 PLANS. A REVISION IS REQUIRED FOR NEW INFORMATION ADDED
 TO THE PLANS. SECTION 106.1.3. THE EXISTING SHEET A-1
 WITH THE FOOD SERVICE APPROVAL STAMP CAN BE RESUBMITTED
 IN THE PLANS AS A REFERENCE SHEET ONLY. -- IF THE WHS'S
 ARE TO BE INSTALLED, THEN THE PLUMBING PLANS SHALL
 REFLECT THE INSTALLATION.
  
 3. A GREASE INTERCEPTOR IS INDICATED. THE GREASE
 INTERCEPTOR SHALL BE APPROVED BY THE UTILITY DEPT.
 INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT HOLLY MCGRATH, LABORATORY SUPERVISOR,
 (561) 822-2271, (FAX) (561) 822-2279, OR E-MAIL
 [email protected]. A WRITTEN DETERMINATION OR E-MAIL OF
 APPROVAL IS REQUIRED FOR OUR FILES. ARTICLE III SECTION
 90-124(7) & SECTION 1003.2.
  
 4. SHTS P-1 & P-2. THE JANITOR SINK SHALL DISCHARGE
 THROUGH THE GREASE INTERCEPTOR. SECTION 1003.1.
  
 5. THE DISHWASHER IS PROHIBITED FROM DRAINING INTO THE
 GREASE LINE AND SHALL CONNECT TO THE SANITARY LINE.
 ARTICLE III SECTION 90-124(7)(B).
  
 6. IF THERE IS A FOOD WASTE GRINDER CONNECTING TO THE
 GREASE INTERCEPTOR, THEN A SOLIDS INTERCEPTOR IS
 REQUIRED. SECTION 1003.3.2.
  
 7. GREASE INTERCEPTORS SHALL BE EQUIPPED WITH DEVICES
 TO CONTROL THE RATE OF WATER FLOW SO THAT THE WATER
 FLOW DOES NOT EXCEED THE RATED FLOW. SECTION
 1003.3.4.2.
  
 8. INFORMATIONAL: A SEPARATE GREASE INTERCEPTOR PERMIT
 IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  