| 2009-07-29 09:21:54 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. NEED PERMIT APPLICATION FROM APPROPRIATELY LICENSED |
| | CONTRACTOR FOR THE PROPOSED SCOPE OF WORK (KITCHEN HOOD |
| | AND VENTILATION SYSTEM). ALSO, SEPARATE PLANS AND |
| | PERMIT APPLICATION REQUIRED FOR HOOD SUPPRESSION SYSTEM |
| | IN ACCORDANCE WITH FBC-M 509.1. |
| | |
| | 2. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10 |
| | FEET HORIZONTALLY FROM PARTS OF THE SAME OR CONTIGUOUS |
| | BUILDINGS, ADJACENT BUILDINGS, ADJACENT PROPERTY LINES |
| | AND AIR INTAKE OPENINGS INTO ANY BUILDING IN ACCORDANCE |
| | WITH FBC-M 506.3.12.3. PROVIDE PLAN VIEW OF ROOF |
| | SHOWING LOCATION OF ADJACENT BUILDINGS, OPENINGS AND |
| | PROPERTY LINES. |
| | |
| | 3. MAKEUP AIR FAN INTAKE IS SHOWN TO BE LOCATED AT THE |
| | REAR OF THE BUILDING WHICH DIRECTLY ABUTS AN ALLEY. |
| | MAKEUP AIR INTAKE OPENING LOCATION SHALL COMPLY WITH |
| | SECTIONS 401.4 AND 401.4.1 OF THE FBC-M (MINIMUM 10' |
| | FROM ALLEYS, STREETS OR PARKING LOTS) IN ACCORDANCE |
| | WITH FBC-M 508.1. |
| | |
| | 4. DWG #3 SHOWS EXHAUST FAN ON A 7/12 PITCHED ROOF. A |
| | LEVEL PLATFORM SHALL BE PROVIDED ON EACH SIDE OF THE |
| | APPLIANCE TO WHICH ACCESS IS REQUIRED FOR SERVICE, |
| | REPAIR OR MAINTENANCE. THE PLATFORM SHALL BE NOT LESS |
| | THAN 30 INCHES IN ANY DIMENSION AND SHALL BE PROVIDED |
| | WITH GUARDS. THE GUARDS SHALL EXTEND NOT LESS THAN 42 |
| | INCHES ABOVE THE PLATFORM, SHALL BE CONSTRUCTED SO AS |
| | TO PREVENT THE PASSAGE OF A 21-INCH-DIAMETER SPHERE AND |
| | SHALL COMPLY WITH THE LOADING REQUIREMENTS FOR GUARDS |
| | SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING IN |
| | ACCORDANCE WITH FBC-M 306.5.1. |
| | |
| | 5. A RECEPTACLE OUTLET SHALL BE PROVIDED AT OR NEAR THE |
| | EQUIPMENT LOCATION IN ACCORDANCE WITH THE CHAPTER 27 OF |
| | THE FLORIDA BUILDING CODE, BUILDING AND FBC-M 306.5.2. |
| | |
| | 6. PROVIDE CERTIFICATION FROM STRUCTURAL ENGINEER THAT |
| | EXISTING ROOF TRUSSES ARE CAPABLE OF SUPPORTING THE |
| | ADDITIONAL GRAVITY LOADS OF THE HOOD, SUPPRESSION |
| | SYSTEM, SUPPLY AND EXHAUST DUCTWORK, SUPPLY AND EXHAUST |
| | FANS, FIRE WRAP AND OTHER RELATED COMPONENTS IN |
| | ACCORDANCE WITH FBC-EB 707.4.1. |
| | |
| | 7. PLEASE PROVIDE PRODUCT APPROVAL FOR WALL LOUVER. |
| | RULE 9B-72 PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | RONALD J. REGUEIRO |
| | 561.805.6719 |
| | [email protected] |
| | |
| | |