Plan Review Notes
Plan Review Notes For Permit 09060251
Permit Number 09060251
Review Stop M
Sequence Number 1
Notes
Date Text
2009-07-29 09:21:54REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NEED PERMIT APPLICATION FROM APPROPRIATELY LICENSED
 CONTRACTOR FOR THE PROPOSED SCOPE OF WORK (KITCHEN HOOD
 AND VENTILATION SYSTEM). ALSO, SEPARATE PLANS AND
 PERMIT APPLICATION REQUIRED FOR HOOD SUPPRESSION SYSTEM
 IN ACCORDANCE WITH FBC-M 509.1.
  
 2. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10
 FEET HORIZONTALLY FROM PARTS OF THE SAME OR CONTIGUOUS
 BUILDINGS, ADJACENT BUILDINGS, ADJACENT PROPERTY LINES
 AND AIR INTAKE OPENINGS INTO ANY BUILDING IN ACCORDANCE
 WITH FBC-M 506.3.12.3. PROVIDE PLAN VIEW OF ROOF
 SHOWING LOCATION OF ADJACENT BUILDINGS, OPENINGS AND
 PROPERTY LINES.
  
 3. MAKEUP AIR FAN INTAKE IS SHOWN TO BE LOCATED AT THE
 REAR OF THE BUILDING WHICH DIRECTLY ABUTS AN ALLEY.
 MAKEUP AIR INTAKE OPENING LOCATION SHALL COMPLY WITH
 SECTIONS 401.4 AND 401.4.1 OF THE FBC-M (MINIMUM 10'
 FROM ALLEYS, STREETS OR PARKING LOTS) IN ACCORDANCE
 WITH FBC-M 508.1.
  
 4. DWG #3 SHOWS EXHAUST FAN ON A 7/12 PITCHED ROOF. A
 LEVEL PLATFORM SHALL BE PROVIDED ON EACH SIDE OF THE
 APPLIANCE TO WHICH ACCESS IS REQUIRED FOR SERVICE,
 REPAIR OR MAINTENANCE. THE PLATFORM SHALL BE NOT LESS
 THAN 30 INCHES IN ANY DIMENSION AND SHALL BE PROVIDED
 WITH GUARDS. THE GUARDS SHALL EXTEND NOT LESS THAN 42
 INCHES ABOVE THE PLATFORM, SHALL BE CONSTRUCTED SO AS
 TO PREVENT THE PASSAGE OF A 21-INCH-DIAMETER SPHERE AND
 SHALL COMPLY WITH THE LOADING REQUIREMENTS FOR GUARDS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING IN
 ACCORDANCE WITH FBC-M 306.5.1.
  
 5. A RECEPTACLE OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT LOCATION IN ACCORDANCE WITH THE CHAPTER 27 OF
 THE FLORIDA BUILDING CODE, BUILDING AND FBC-M 306.5.2.
  
 6. PROVIDE CERTIFICATION FROM STRUCTURAL ENGINEER THAT
 EXISTING ROOF TRUSSES ARE CAPABLE OF SUPPORTING THE
 ADDITIONAL GRAVITY LOADS OF THE HOOD, SUPPRESSION
 SYSTEM, SUPPLY AND EXHAUST DUCTWORK, SUPPLY AND EXHAUST
 FANS, FIRE WRAP AND OTHER RELATED COMPONENTS IN
 ACCORDANCE WITH FBC-EB 707.4.1.
  
 7. PLEASE PROVIDE PRODUCT APPROVAL FOR WALL LOUVER.
 RULE 9B-72 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
  