Plan Review Notes
Plan Review Notes For Permit 09060251
Permit Number 09060251
Review Stop G
Sequence Number 1
Notes
Date Text
2009-07-02 14:09:52DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. A SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE
 REQUIRED INFORMATION FOR THE PERMIT:
  
 1. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407.
 -- REQUIRED FOR THE WATER HEATER.
  
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2007 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 B. SHT P-2 NATURAL GAS RISER DIAGRAM. PIPE SIZE TO ITEM
 10 SHALL BE 1-1/2" (FOR 455,000 BTU'S AT 80') AND THE
 STUB OUT FOR ITEM 10 IS REQUIRED TO BE 1-1/4" UP TO AND
 INCLUDING THE SHUT OFF VALVE. TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  