Plan Review Notes
Plan Review Notes For Permit 09060251
Permit Number 09060251
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-05 13:06:12 
 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLEASE SEE COVER SHEET WHICH REFLECTS THE
 CONTRACTOR AS CBT CONSTRUCTION HOWEVER THE PERMIT
 APPLICATION STATES HORGAN GENERAL CONTR.
 THE CONTRACTOR IS NOT REQUIRED TO BE NOTED ON PLANS.;
 THIS IS NOT A CODE REQUIRED ITEM ONLY FOR COORDINATION
 OF RECORD PLANS.
  
 2) NOTE: PLANS NEED TO STATE THE FOLLOWING CODES
 SUBMITTED AFTER MARCH 1ST, 2009
 AT THIS TIME THERE ARE REFERENCES TO CODES WHICH ARE NO
 LONGER APPLICABLE. PLEASE ALSO KNOW THAT STATING *THE
 LATEST EDITION* IS NOT ACCEPTABLE. THERE ARE MANY
 INSTANCES WHERE THE LATEST EDITION IN PUBLICATION IS
 NOT ADOPTED OR IS NEVER ADOPTED.
 ALL RECORD SET OF PLANS IS REQUIRED BY LAW AND FBC TO
 STATE THE CODES RELEVANT TO THE SPECIFIC PROJECT AND
 DESIGN.
 PLEASE LIST AND DESIGN PER THE FOLLOWING ADOPTED CODES
 AT THIS TIME FOR THIS REVIEWER. THERE MAY BE OTHER
 CODES REQUESTED BY OTHER TRADES.
  
 2007 FBC WITH 2009 SUPPLEMENTS.
 2005 NFPA_70
 2006 NFPA-101
 2002 NFPA-72
  
 PER FS 633,553.73,FAC 69A-60.004, 69A-3.0125 ETC
  
 3) NOTE: ONE COMPLETE SET OF PLANS FOR MEP DESIGNERS
 ARE *PHOTO-COPIES* OF SIGNED, DATED AND SEALED PLANS.
 PLEASE SEE FAC 61G15-23.002 AS THIS IS NOT PERMITTED.
 BOTH SETS FOR THE MEP DESIGN PROFESSIONAL SHALL BE
 ORIGINAL.
 FS 471.025
 PLEASE BE SURE TO ADDRESS FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
  
 4) NOTE: SCOPE OF WORK IS NOT CLEAR. SOME AREAS ARE
 INDICATING NO WORK HOWEVER OTHER DETAILS ON PLANS SEEM
 TO INDICATE WORK IN THOSE SAME AREAS.
 SOME OF WHAT IS SHOWN AS EXISTING TO REMAIN IS NOT AT
 LOCATION OR DIFFERENT.
 MANY ITEMS ON PLANS ARE SO LIGHT THAT EXISTING CODE
 COMPLIANCE CAN NOT BE VERIFIED AS SAFE FOR NEW
 OCCUPANCY. THE FIRE ALARM DEVICE LOCATIONS FOR EXAMPLE
 ARE ONE EXAMPLE OF THIS.
 PLEASE SEE FBC FOR REQUIRED SYSTEMS AND NFPA72 FOR
 MINIMUM INSTALLATIONS.
 PLEASE SEE FBC 11-4.28.1,2 AND .3.
  
 5) NOTE: PLEASE SUBMIT PLANS SHOWING COMPLETE EGRESS
 LIGHTING AND EXIT LIGHTING REQUIREMENTS PER NFPA-101
 2006 EDITION, 7.8, 7.9, FBC 1016, NEC 700.16,700.12F.
 BATHROOMS DO NOT SHOW ANY LIGHTING FOR EMERGENCY
 EGRESS. IS IT NEW OR EXISTING?
  
 6) NOTE: PLEASE COORDINATE RISER AND PANELS.
 PANEL B SHOWN AS 250AMP YET RISER INDICATES 225AMP.
 215.5,230,240,310 GIVEN IN GENERAL.
 FBC 106.1.1, 106.1.2, 106.5 FOR CLARITY, COORDINATION
 OF RECORD PLANS.
  
 7) NOTE: PLEASE SEE NEC 220.43 FOR TRACK LIGHTING AND
 SHOW WINDOW LOADS WHICH ARE REQUIRED TO BE SHOWN.
  
 8) NOTE: THE PLANS STATES THAT THE CONTRACTOR SHALL
 REMOVE ALL OLD WIRING WHICH IS NO LONGER IN USE WHEN
 ACCESSIBILITY IS IMPAIRED. PLEASE SEE NEC CHAPTER 8,
 800.3C,
  
 *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE
 PERMITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  