| 2009-07-13 14:59:44 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. THERE DO NOT APPEAR TO BE ANY PROVISIONS FOR |
| | VENTILATION ON PLANS. THE MINIMUM VENTILATION RATE OF |
| | OUTDOOR AIR SHALL BE DETERMINED IN ACCORDANCE WITH |
| | FBC-M SECTION 403.3. PROVIDE VENTILATION CALCULATIONS |
| | TO DETERMINE THE REQUIRED RATE OF VENTILATION FOR EACH |
| | SPACE IN ACCORDANCE WITH FBC-M TABLE 403.3. SHOW MEQANS |
| | AND LOCATION OF VENTILATION AIR INTAKE IN ACCORDANCE |
| | WITH FBC-M 401.4. |
| | |
| | 2. PAGE A2 SHOWS AN EXHAUST FAN ON THE PLANS BUT NO |
| | INFORMATION IS PROVIDED REGARDING THE FAN. PROVIDE FAN |
| | DATA SHOWING THE EXHAUST RATE IN ACCORDANCE WITH FBC-M |
| | TABLE 403.3. ALSO, SHOW THE MEANS AND LOCATION OF |
| | EXHAUST DUCT DISSCHHARGE IINCORDANCE WITH FBC-M 401.4 |
| | AND FBC-M 501.2. |
| | |
| | 3. A RETURN AIR TRANSFER DUCT IS SHOWN FOR THE |
| | CONFERENCE ROOM. THE TRANSFER DUCT IS NOT SIZED IN |
| | ACCORDANCE WITH THE EXCEPTIONS UNDER FBC-M 601.4. SIZE |
| | THIS RETURN TRANSFER DUCT IN ACCORDANCE WITH THE |
| | EXCEPTIONS OR A FIELD TEST WILL BE REQUIRED AT TIME OF |
| | FINAL INSPECTION TO DETERMINE THE ACTUAL PRESSURE |
| | DIFFERENTIAL ACROSS THE CLOSED DOOR. |
| | |
| | 4. EQUIPMENT SCHEDULE CALLS FOR AHU TO PROVED 2000 CFM |
| | OF SUPPLY WHILE FLOOR PLAN ONLY CALLS FOR 1540 CFM. |
| | WHICH IS CORRECT? PLEASE COORDINATE FLOOR PLAN AND |
| | EQUIPMENT SCHEDULE ENSURING EQUIPMENT IS PROPERLY SIZED |
| | FOR THE COOLING LOADS IN ACCORDANCE WITH FBC-M 312.1. |
| | NOTE: THE MODEL NUMBERS LISTED ON THE SCHEDULE INDICATE |
| | A 4 TON SYSTEM. IF A 5 TON SYSTEM IS INSTALLED, PROVIDE |
| | DUCT SMOKE DETECTOR ON SUPPLY SIDE IN ACCORDANCE WITH |
| | FBC-M 606.2.1. |
| | |
| | 5. CONDENSING UNIT STAND INFORMATION ON PLANS IS |
| | OUT-DATED AND PARTIALLY ILLEGIBLE. PLEASE SUBMIT AN |
| | ACTUAL CURRENT PRODUCT APPROVAL OR THE PROPOSED STAND, |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD IN |
| | ACCORDANCE WITH FBC-B 106.3.3. |
| | |
| | 6. ENERGY CODE COMPLIANCE FORM SUBMITTED IS OUT OF |
| | DATE. THE CORRECT FORM IS 400B-08 AS OF MARCH 1, 2009. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |
| | RONALD J. REGUEIRO |
| | 561.805.6719 |
| | [email protected] |