| 2009-07-04 08:36:45 | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER |
| | ADOPTION BY THE STATE OF FLORIDA. |
| | PLEASE SEE FAC 69A-60.004 AND 69A-3.012 AS THE |
| | APPLICABLE NFPA-101 IS THE 2006. PLANS SHOW 2003. |
| | |
| | 2) NOTE: THE SUBMITTED FORM FOR ENERGY CODE COMPLIANCE |
| | IS FROM THE 2004 FBC. PLEASE KNOW THAT UNDER THE 2007 |
| | FBC WITH 2009 REVISIONS THERE IS NO LONGER A METHOD |
| | *C*. ALL PERMIT APPLICATIONS AFTER MARCH 1ST, 2009 NEED |
| | TO BE UNDER THE REVISED FBC CHAPTER 13. |
| | PLEASE SEE 13-415.AB.5 FOR LIGHTING PERFORMANCE |
| | CALCULATIONS AND LEVELS PERMITTED. |
| | IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL. |
| | PLEASE KEEP IN MIND A FIXTURE LEGEND WITH SPECIFIC |
| | FIXTURES IS NEEDED TO VERIFY MINIMUM CODE COMPLIANCE. |
| | |
| | 3) NOTE: PLEASE SEE 13-415.AB.1.2 FOR ROOMS WHICH ARE |
| | REQUIRED TO CONTAIN AUTOMATED LIGHTING CONTROLS WHETHER |
| | OR NOT THEY ARE IN A BUILDING GREATER THAN 5K SQ FT. T |
| | THIS WOULD BE THE KITCHEN/BREAK ROOM, CONFERENCE ROOM. |
| | |
| | 4) NOTE: PLEASE SEE 422.13 OF THE 2005 NEC. WATER |
| | HEATER LOAD IS CONSIDERED A CONTINUOUS LOAD WHICH |
| | REQUIRES LOAD TO BE SHOWN AND FIGURED AT 125%. |
| | |
| | 5) NOTE: PLEASE SEE 600.5 FOR REQUIRED SIGN CIRCUIT. |
| | THIS DOES NOT REQUIRE A SIGN TO BE INSTALLED ONLY |
| | PROVISIONS FOR CIRCUIT AT FRONT DOOR AREA LOCATION. |
| | ( VA TO BE FIGURED IS 1200VA) |
| | |
| | 6) NOTE: THE LOAD CALCULATIONS SHOWN ON PLANS IS BASED |
| | ON A RESIDENTIAL HOUSE. PLEASE SEE NEC |
| | 220.12,220.14,220.42,220.44, 220.43,220.56,220.60, ETC |
| | AND 215.3, 230.42 FOR ALL OTHER CONTINUOUS LOADS AND |
| | LARGEST MOTOR LOADS AT 125%. |
| | |
| | 7) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EXIT AND |
| | EMERGENCY LIGHTS. NO CIRCUITING SHOWN, MUST BE TO LOCAL |
| | LIGHTING BRANCH CIRCUIT. |
| | |
| | 8) NOTE: PLEASE SEE 13-415.AB.1.4 FOR EXTERIOR LIGHTING |
| | CONTROLS. MAY NOT BE ONLY A SINGLE POLE SWITCH. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |