2009-06-18 13:45:10***DENIED***
  
 1) SHEET 1 ILLUSTRATES AN EXISTING FIRE HYDRANT LOCATED
 199' FROM THE NEW FIRE DEPARTMENT CONNECTION WHICH
 SHALL NOT BE GREATER THAN 150' FROM THE CLOSEST FIRE
 HYDRANT. NO OTHER FIRE HYDRANTS ARE SHOWN ON THE PLANS.
  
 2) NEW FIRE DEPARTMENT CONNECTIONS ARE REQUIRED TO BE
 PROVIDED WITH KNOX LOCKING CAPS. PLEASE CONTACT THE
 BUREAU OF FIRE PREVENTION FOR ASSISTANCE AT (561)
 804-4724.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756