| Plan Review Notes For Permit 09060200 |
| Permit Number |
09060200 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-18 13:45:10 | ***DENIED*** | | | | | | 1) SHEET 1 ILLUSTRATES AN EXISTING FIRE HYDRANT LOCATED | | | 199' FROM THE NEW FIRE DEPARTMENT CONNECTION WHICH | | | SHALL NOT BE GREATER THAN 150' FROM THE CLOSEST FIRE | | | HYDRANT. NO OTHER FIRE HYDRANTS ARE SHOWN ON THE PLANS. | | | | | | 2) NEW FIRE DEPARTMENT CONNECTIONS ARE REQUIRED TO BE | | | PROVIDED WITH KNOX LOCKING CAPS. PLEASE CONTACT THE | | | BUREAU OF FIRE PREVENTION FOR ASSISTANCE AT (561) | | | 804-4724. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|