Plan Review Notes
Plan Review Notes For Permit 09060193
Permit Number 09060193
Review Stop E
Sequence Number 2
Notes
Date Text
2009-08-10 14:59:04 
  
 ** DENIED REVIEW **
 2ND REVIEW
  
  
 PLEASE SEE THAT SOME NOTES FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 SOME NEW NOTES ARE ALSO NOW CREATED BASED ON SOME
 REVISIONS MADE NOT PART OF PREVIOUS PLANS.
 ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES. PLEASE REVISE AT THIS TIME.
  
 1) NOTE: PLEASE INDICATE THE AIC RATING OF SERVICE
 EQUIPMENT. 110.9
 ALL EQUIPMENT MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
 PREVIOUS NOTES
  
 2) NOTE: PLEASE INDICATE THE REQUIRED ARC FAULT
 PROTECTION FOR ALL OUTLETS. THE PANEL SCHEDULE WAS
 REVISED HOWEVER ONLY INDICATES THE AFCI PROTECTION FOR
 RECEPTACLES. 210.12
 PREVIOUS NOTES
  
 3) NOTE: PLEASE SEE MISSING *EQUIPMENT GROUNDING
 CONDUCTOR* FROM MAIN TO PANEL.
 250.122
  
 4) NOTE: THE GROUNDING ELECTRODE INDICATES ATTACHMENT
 TO GAS LING AS PART OF THE GROUNDING ELECTRODE. THIS IS
 NOT PERMITTED. THE GAS LINE IS BONDED PER 250.104
 HOWEVER NOT PART OF THE GROUNDING ELECTRODE SYSTEM. THE
 NOTE ON THE SAME STATES *OR* FOOTER STEEL. PLEASE SEE
 250.50 AS THE NEW FOOTER STEEL IS REQUIRED. PLEASE CALL
 TO ADJUST NOTES ON RISER.
  
 5) NOTE: PLEASE CIRCUITS 4,6 AND 8,10 ARE
 REVERSED.408.4
  
 6) NOTE: PLANS SHOW SMOKE DETECTORS, PLEASE VERIFY THIS
 AS THESE WOULD BE SMOKE ALARMS. PLEASE ALSO SEE PLANS
 ARE MISSING CARBON MONOXIDE DETECTORS. FS 553.885
  
 7) NOTE: PANEL SHOWN ON PLANS IS SHOWN NOT MEETING
 110.26. COVER IS SHOWN IN THE DIRECTION FACING THE
 COUNTER SPACE IN KITCHEN AREA.
 MUST HAVE CLEAR FLOOR SPACE AND WORKING CLEARANCES.
  
 8) NOTE: PLEASE SEE 210.11C2, 220. 52 AS THE MINIMUM
 LOAD FOR WASHER/LAUNDRY NEEDS TO BE 1500VA.
  
  
 ** PLANS ARE NO LONGER RELEASED PER BUILDING DIRECTOR.
 A TIME WILL NEED TO BE SET UP TO BRING IN NEW REVISIONS
 AND CHANGE OUT SHEETS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  