| 2009-08-10 14:59:04 | |
| | |
| | ** DENIED REVIEW ** |
| | 2ND REVIEW |
| | |
| | |
| | PLEASE SEE THAT SOME NOTES FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | SOME NEW NOTES ARE ALSO NOW CREATED BASED ON SOME |
| | REVISIONS MADE NOT PART OF PREVIOUS PLANS. |
| | ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER |
| | TRADES. PLEASE REVISE AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE INDICATE THE AIC RATING OF SERVICE |
| | EQUIPMENT. 110.9 |
| | ALL EQUIPMENT MUST BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT. |
| | PREVIOUS NOTES |
| | |
| | 2) NOTE: PLEASE INDICATE THE REQUIRED ARC FAULT |
| | PROTECTION FOR ALL OUTLETS. THE PANEL SCHEDULE WAS |
| | REVISED HOWEVER ONLY INDICATES THE AFCI PROTECTION FOR |
| | RECEPTACLES. 210.12 |
| | PREVIOUS NOTES |
| | |
| | 3) NOTE: PLEASE SEE MISSING *EQUIPMENT GROUNDING |
| | CONDUCTOR* FROM MAIN TO PANEL. |
| | 250.122 |
| | |
| | 4) NOTE: THE GROUNDING ELECTRODE INDICATES ATTACHMENT |
| | TO GAS LING AS PART OF THE GROUNDING ELECTRODE. THIS IS |
| | NOT PERMITTED. THE GAS LINE IS BONDED PER 250.104 |
| | HOWEVER NOT PART OF THE GROUNDING ELECTRODE SYSTEM. THE |
| | NOTE ON THE SAME STATES *OR* FOOTER STEEL. PLEASE SEE |
| | 250.50 AS THE NEW FOOTER STEEL IS REQUIRED. PLEASE CALL |
| | TO ADJUST NOTES ON RISER. |
| | |
| | 5) NOTE: PLEASE CIRCUITS 4,6 AND 8,10 ARE |
| | REVERSED.408.4 |
| | |
| | 6) NOTE: PLANS SHOW SMOKE DETECTORS, PLEASE VERIFY THIS |
| | AS THESE WOULD BE SMOKE ALARMS. PLEASE ALSO SEE PLANS |
| | ARE MISSING CARBON MONOXIDE DETECTORS. FS 553.885 |
| | |
| | 7) NOTE: PANEL SHOWN ON PLANS IS SHOWN NOT MEETING |
| | 110.26. COVER IS SHOWN IN THE DIRECTION FACING THE |
| | COUNTER SPACE IN KITCHEN AREA. |
| | MUST HAVE CLEAR FLOOR SPACE AND WORKING CLEARANCES. |
| | |
| | 8) NOTE: PLEASE SEE 210.11C2, 220. 52 AS THE MINIMUM |
| | LOAD FOR WASHER/LAUNDRY NEEDS TO BE 1500VA. |
| | |
| | |
| | ** PLANS ARE NO LONGER RELEASED PER BUILDING DIRECTOR. |
| | A TIME WILL NEED TO BE SET UP TO BRING IN NEW REVISIONS |
| | AND CHANGE OUT SHEETS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |