| 2009-08-12 13:09:22 | 2007 FBC W/2009 SUPPLEMENTS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. 233-5025 |
| | |
| | 2) PLEASE REVISE THE CODE INFORMATION ON THE PLANS TO |
| | THE 2007 FBC W/2009 SUPPLEMENT. THIS IS THE CODE |
| | EDITION THAT APPLIES TO THIS PROJECT. SEE UNDER SCOPE |
| | OF WORK ON SHEET A01. |
| | |
| | 3) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF |
| | COVERING MATERIALS ( SLOPED AND FLAT), SINGLE GLAZED |
| | OUTSWING DOOR AND FRENCH DOORS AS REQUIRED BY DCA RULE |
| | 9B-72. |
| | NOTE: ON THE FLAT ROOF PRODUCT APPROVAL SPECIFY THE |
| | APPROVED SYSTEM AND FASTENING OPTION THAT WILL BE USED |
| | AND ENHANCED FASTENING REQUIREMENTS IF REQUIRED BY |
| | LIMITATION #7 ON THE NOA. |
| | |
| | 4) THE PRODUCT APPROVALS SUBMITTED FOR THE GAF ROOF |
| | SHINGLES ARE FOR THE 2004 CODE AND ONLY THE FLORIDA |
| | COVER SHEETS WERE SUBMITTED. SUBMIT 2 COPIES OF PRODUCT |
| | APPROVALS FOR THE 2007 FBC INCLUDE THE EVALUATIONS OR |
| | NOAS. SEE FL 10124-R1. |
| | |
| | 5) THE PRODUCT APPROVALS SUBMITTED FOR THE FIRESTONE |
| | MODIFIED ROOF SYSTEM IS FOR THE 2004 FBC. SUBMIT TWO |
| | COPIES FOR THE 2007 FBC INCLUDING TWO COPIES OF THE |
| | NOA. ONLY ONE COPY OF THE NOA WAS SUBMITTED AND IT HAS |
| | BEEN REVISED BY NOA 08-0118.07. SPECIFY THE ASSEMBLY |
| | THAT WILL BE INSTALLED AND PROVIDE RAS117 CALCULATIONS |
| | FOR ENHANCED FASTENING. |
| | |
| | 6) THE PLANS SPECIFY RECONDITIONED DOORS AND WINDOWS |
| | INSTALLED INTO NEW OPENINGS. ALL EXTERIOR WINDOWS AND |
| | DOORS ARE CONSIDERED COMPONENTS AND CLADDING AND ARE |
| | REQUIRED TO HAVE PRODUCT APPROVALS OR SITE SPECIFIC |
| | ENGINEERING BY DCA RULE 9B-72. |
| | |
| | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS, KEY PLANS |
| | AND INSTALLATION SCHEDULES FOR THE STORM PANELS. |
| | SPECIFY THE MOUNTING TYPE, THE FASTENER TYPE, FASTENER |
| | SPACING, GLASS SEPARATION, EDGE DISTANCE, ETC. RULE |
| | 9B-72 |
| | |
| | 8) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE |
| | ADDITION. FBC 13-101.2.2 THE ONES SUBMITTED ARE ON 2004 |
| | FBC FORMS AND ARE NO LONGER ACCEPTABLE. SUBMIT FORMS |
| | REQUIRED BY THE 2007 FBC ENERGY GLITCH AMENDMENTS. |
| | |
| | 9) THE ENGINEERING SUBMITTED FOR THE EXISTING STORM |
| | PANELS IS NOT ACCEPTABLE. SEE DCA RULE 9B-72. |
| | |
| | NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE FENCE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |