| Notes |
| Date |
Text |
| 2009-07-08 13:53:18 | 2007 FBC W/2009 AMENDMENTS | | | ADDITION | | | | | | DENIED BY MECHANICAL | | | | | | 1) RETURN AIR SHALL NOT BE TAKEN FROM A BATHROOM. FBC | | | RESIDENTIAL M1602.2. | | | | | | 2) THE PLAN SHOWS A SUPPLY DUCT FROM A GRILL IN THE | | | MASTER BEDROOM TO THE SUPPLY DUCT IN THE NEW BATHROOM. | | | IS THE GRILL IN THE BEDROOM EXISTING. IF SO, PLEASE | | | LABEL THE GRILL AS EXISTING. ALSO THERE IS NO NEED TO | | | SHOW THE DUCT RUNNING FROM THE BEDROOM GRILL TO THE | | | BATHROOM GRILL. JUST SHOW THE NEW SUPPLY GRILL IN THE | | | BATHROOM WITH THE NOTE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|