Plan Review Notes
Plan Review Notes For Permit 09060193
Permit Number 09060193
Review Stop M
Sequence Number 1
Notes
Date Text
2009-07-08 13:53:182007 FBC W/2009 AMENDMENTS
 ADDITION
  
 DENIED BY MECHANICAL
  
 1) RETURN AIR SHALL NOT BE TAKEN FROM A BATHROOM. FBC
 RESIDENTIAL M1602.2.
  
 2) THE PLAN SHOWS A SUPPLY DUCT FROM A GRILL IN THE
 MASTER BEDROOM TO THE SUPPLY DUCT IN THE NEW BATHROOM.
 IS THE GRILL IN THE BEDROOM EXISTING. IF SO, PLEASE
 LABEL THE GRILL AS EXISTING. ALSO THERE IS NO NEED TO
 SHOW THE DUCT RUNNING FROM THE BEDROOM GRILL TO THE
 BATHROOM GRILL. JUST SHOW THE NEW SUPPLY GRILL IN THE
 BATHROOM WITH THE NOTE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]