Plan Review Notes
Plan Review Notes For Permit 09060193
Permit Number 09060193
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-19 10:54:50 
 ** DENIED PLANS *
  
 1) NOTE: PLANS SUBMITTED STATE THE 2004 FBC W/ 2006
 REVISIONS. PLEASE KNOW THAT ALL PLANS SUBMITTED ON OR
 AFTER MARCH 1ST 2009 SHALL BE UNDER THE DESIGN OF THE
 2007 FBC W/ 2009 AMENDMENTS.
 THE PLANS NEED TO STATE THE FOLLOWING CODES AT A
 MINIMUM FOR THIS REVIEWER AS APPLICABLE TO ELECTRICAL
 PLANS.
 2007 FBC W/2009 REVISION
 2005 NFPA-70 ( NEC)
 2002 NFPA-72
  
  
 2) NOTE: PLEASE SEE FBC R313.1, NFPA-72 2002. PROVIDE A
 COMPLETE LAYOUT OF NEW OR EXISTING SMOKE ALARMS MEETING
 THE CURRENT NFPA-72 11.5.1.1, 11.8.3.
 THE PLANS DO NOT SHOW ANY NEW OR EXISTING FOR ADDITION
 OR REMODEL.
 PLEASE BE SURE TO ALSO SEE NEC 210.12 FOR ARC FAULT
 PROTECTION REQUIRED. 210.12 SEE OTHER NOTES.
  
 3) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH
 THE SUBMITTED PANEL SCHEDULE. THERE ARE NUMEROUS
 INCONSISTENCIES ON PLANS WITH THE SUBMITTED PANEL
 SCHEDULE. BELOW WILL BE SOME EXAMPLES.
  
 FOR EXAMPLE: ALL CIRCUITS ARE NOTES AS *C* WHEN THE
 PANEL IS PANEL *A*.
 FOR EXAMPLE: THE OUTSIDE CONDENSING UNIT IS SHOWN AS AN
 AIR HANDLER AND THE CIRCUIT WHICH IS SHOWN AS C 12-14.
 FOR EXAMPLE: PLEASE SEE THE UNIDENTIFIED EQUIPMENT IN
 THE UTILITY CLOSET WHICH IS LABELED CIRCUIT C-5,7
 HOWEVER IF YOU LOOK AT THE PANEL SCHEDULE FOR THIS SAME
 ITEM IT IS THE SMALL APPLIANCE AND DISHWASHER/DISPOSAL
 CIRCUIT. THIS IS NOT PERMITTED OR POSSIBLE. SMALL
 APPLIANCE CIRCUITS ARE NOT PERMITTED TO FEED ANY OTHER
 AREAS. 210.52B1
 THIS SAME CIRCUIT C 5.7 IS ALSO SHOWN IN MORE THAN ONE
 LOCATION.
 FOR EXAMPLE: CIRCUIT C-32 IS SHOWN AS FEEDING LANDSCAPE
 LIGHTING HOWEVER PER THE PLANS THIS IS LIGHTING LOCATED
 INSIDE THE HOUSE.
  
 ** THIS IS ONLY A FEW EXAMPLES; PLEASE BE SURE TO SEE
 THE REST OF THE COMMENTS AND COORDINATE ALL.
 408..4,250.52,240.4,310.16 ETC
  
 4) NOTE: PLEASE SUBMIT LOAD CALCULATIONS IN ACCORDANCE
 WITH THE MINIMUM CODE FROM THE NEC. THERE ARE ITEMS
 WHICH ARE MISSING COMPLETELY.
 FOR EXAMPLE: THE DRYER IS SHOWN ON THE PANEL SCHEDULE
 IS NOT IN THE LOAD CALCULATIONS. PLEASE SEE 220.54 FOR
 MINIMUM LOAD REQUIRED TO BE FIGURED.
 FOR EXAMPLE: AS THERE APPEARS TO BE A WATER HEATER ON
 PLANS IT IS NOT CLEAR IF IT IS GAS OR ELECTRICAL.
 PLEASE SEE 4220.13 OF THE 2005 NEC AS THE WATER HEATER
 IS NOW CONSIDERED A CONTINUOUS IF ELECTRICAL. PLEASE
 ADJUST LOAD CALCULATIONS ACCORDINGLY. 422.13
 FOR EXAMPLE; THE AHU HEAT NEEDS TO BE COORDINATED. SEE
 NOTE #11 BELOW.
 * PLEASE SEE NEC 220. THERE ARE OTHER ITEMS SUCH AS THE
 ONE OR MORE *SMALL APPLIANCE CIRCUITS*, DEDICATED
 CIRCUITS ETC.
 220.53, 220.52 ETC
  
 5) NOTE: PLEASE SEE FS 553.885 FOR REQUIRED CARBON
 MONOXIDE DETECTOR WHICH IS REQUIRED FOR ANY HOUSE WITH
 ATTACHED GARAGE OR GAS APPLIANCES. IT IS NOT KNOWN AT
 THIS TIME IF THERE ARE ANY GAS APPLIANCES AT THIS
 LOCATION.
 BASED ON THE FACT THE PANEL SCHEDULE DOES NOT SHOW ANY
 STOVE, RANGE, OR WATER HEATER IT COULD BE ASSUMED THERE
 IS GAS APPLIANCES FOR THESE????
  
 6) NOTE: PLEASE SEE 210.52F, 210.11C2 AND 220.52 FOR
 MISSING REQUIRED WASHER/LAUNDRY CIRCUIT AND LOADS.
  
 7) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 FOR
 MISSING DINING ROOM CIRCUIT, LOAD ETC.
  
 8) NOTE: PLEASE LIST ALL OF THE REQUIRED ARC FAULT
 CIRCUITS PER 210.12, 408.4
  
 9) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE
 LOCATION OF THE ELECTRICAL PANEL. THIS SEEMS TO BE SOME
 KIND OF STORAGE AREA. PLEASE SEE 240.24D, 110.26 FOR
 LOCATION IN STORAGE AREAS NOT PERMITTED AND WORKING
 CLEARANCES REQUIRED.
  
 10) NOTE: PLEASE IDENTIFY ALL EQUIPMENT AND APPLIANCES
 ON PLANS. AS NOTED ABOVE THE CIRCUIT #5,7 GOES TO
 SOMETHING HOWEVER IT CAN NOT BE DETERMINED WHAT IT IS.
 ALSO THE AHU NEEDS TO BE SHOWN. THERE ARE TWO SQUARE
 BOXES ON PLANS BOTH SHOWING CIRCUITS C-5,7??
 BASED ON THE PLANS THERE IS A SQUARE INSIDE THE CLOSET
 WHICH MAY OR MAY NOT BE THE AHU? PLEASE SEE
 440.11,440.12, 440.14 FOR REQUIRED DISCONNECT TO BE
 SHOWN.
  
 11) NOTE: PLEASE COORDINATE THE AHU WITH THE LOAD,
 CONDUCTORS AND OVER CURRENT PROTECTION. PLEASE SEE
 424.3B, 240.4,310.16, 408.4 ETC
 THE LOAD CALCULATIONS INDICATES THE UNIT AS 7.5 KW
 HOWEVER THE PANEL SCHEDULE SHOWS #10 AWG AND A 25AMP
 BREAKER WHICH DOES NOT MEET THE MINIMUM FOR CODE
 COMPLIANCE. THE OTHER AHU IS SHOWN WITH A 2-POLE 20AMP
 BREAKER AND #12 AWG WHICH IS ALSO NOT PERMITTED FOR
 WHAT APPEARS TO BE A 5KW UNIT.
 THERE ARE SEVERAL ITEMS WHICH NEED TO BE IDENTIFIED AND
 CORRECTED FOR MINIMUM CODE COMPLIANCE.
  
 12) NOTE: PLEASE SEE 110.9 FOR THE AIC RATING WHICH
 NEEDS TO BE SHOWN FOR ALL SERVICE EQUIPMENT.
  
 13) NOTE: PLEASE SEE 250.66 FOR THE MINIMUM SIZE OF THE
 GROUNDING ELECTRODE CONDUCTOR. THE RISER SHOWS #6 WHICH
 DOES NOT MEET MINIMUM CODE.
  
 14) NOTE: PLEASE INCLUDE THE NEW FOOTER STEEL AS
 REQUIRED PER 250.50
  
 15) NOTE: PLEASE SEE 250.104 FOR OTHER METAL PIPING
 WHICH IS REQUIRED TO BE BONDED. ( GAS PIPING??)
  
 16) NOTE: PLEASE SEE PANEL SCHEDULE AS BOTH THE GARBAGE
 DISPOSAL AND THE DISHWASHER IS SHOWN ON THE SAME 1-POLE
 20AMP CIRCUIT WHICH IS NOT PERMITTED. PLEASE SEE
 220.50,430.148, 220.82,220.53 ETC AS THE LOADS ON A
 DISHWASHER IS TYPICALLY AT LEAST 1200VA AND LOADS ON
 DISPOSAL IS GREATER THAN 1/4 HP. BASED ON MINIMUM CODE
 SECTIONS, THESE WOULD BE REQUIRED TO BE ON DEDICATED
 CIRCUITS. PLEASE CONFIRM THAT THESE ARE NOT ACTUALLY ON
 THE SAME CIRCUIT AS THIS IS A SAFETY AND FIRE HAZARD.
 PLEASE ALSO SEE 210.4B FOR DISCONNECTION OF ALL DEVICES
 WITH MULTI-WIRE BRANCH CIRCUITS ON THE SAME YOKE.
  
 17) NOTE: PLEASE SEE 240.4, 310.16 AS THE PANEL
 INDICATES A 30AMP BREAKER ON #12 AWG FOR DRYER.
  
 18) NOTE: PLEASE SEE FBC 13-606 AB .1.2.4 AS ALL NEW
 RECESSED LIGHTING FIXTURES SHALL MEET MINIMUM ENERGY
 CODE REQUIREMENTS PLEASE PLACE NOTE ON PLANS.
  
 19) NOTE: PLEASE SEE 210.52 AS TWO OF THE WALLS IN
 MASTER BEDROOM WILL REQUIRE AN ADDITIONAL RECEPTACLE
 BASED ON THE 3/16 SCALE PROVIDED. IF OVER 12FT THEN
 MORE THAN THE TWO SHOWN WILL BE REQUIRED.
  
 20) NOTE: PLEASE COMPLETE RISER. THERE ARE NO
 CONDUCTORS SHOWN FROM METER TO THE REST OF THE SERVICE.
 215.5, 310.16,310.15B6, 250.110,250.6,250.122 ETC
 FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 21) NOTE: PLEASE GO OVER THE CIRCUITING FOR THE MASTER
 BEDROOM. AS ALL RECEPTACLES, FANS, RECESSED LIGHTS ETC
 ARE SHOWN ON THE SAME CIRCUIT?
 PLEASE SEE 220.12 FOR LIGHTING LOADS. THERE IS OVER 11
 AMPS OF LOAD JUST WITH THE FAN/FAN LTS AND RECESSED
 LIGHTS ALONE.
  
 22) NOTE: PLEASE SEE 210.8A2 AS ALL RECEPTACLES IN
 UTILITY ROOMS ARE REQUIRED TO BE GFI OR GFI PROTECTED.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  