Plan Review Notes
Plan Review Notes For Permit 09060193
Permit Number 09060193
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-08 15:20:202007 FBC W/2009 SUPPLEMENTS
 ADDITION
  
 DENIED BY BUILDING
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025
  
 2) PLEASE REVISE THE CODE INFORMATION ON THE PLANS TO
 THE 2007 FBC W/2009 SUPPLEMENT. THIS IS THE CODE
 EDITION THAT APPLIES TO THIS PROJECT.
  
 3) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF
 COVERING MATERIALS ( SLOPED AND FLAT), SKYLIGHTS AND
 FRENCH DOORS AS REQUIRED BY DCA RULE 9B-72.
 NOTE: ON THE FLAT ROOF PRODUCT APPROVAL SPECIFY THE
 APPROVED SYSTEM AND FASTENING OPTION THAT WILL BE USED
 AND ENHANCED FASTENING REQUIREMENTS IF REQUIRED BY
 LIMITATION #7 ON THE NOA.
  
 4) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR ALL WOOD
 CONNECTORS, STRAPS AND ANCHORS OR SPECIFY THE FL#S ON
 THE PLANS. DCA RULE 9B-72
  
 5) THE PLANS SPECIFY RECONDITIONED DOORS AND WINDOWS
 INSTALLED INTO NEW OPENINGS. ALL EXTERIOR WINDOWS AND
 DOORS ARE CONSIDERED COMPONENTS AND CLADDING AND ARE
 REQUIRED TO HAVE PRODUCT APPROVALS OR SITE SPECIFIC
 ENGINEERING BY DCA RULE 9B-72.
  
 6) PLEASE INDICATE IF THE NEW SHUTTERS ARE DECORATIVE
 OR INTENDED TO PROVIDE IMPACT PROTECTION. IF THEY ARE
 FOR IMPACT PROTECTION, SUBMIT TWO COPIES OF PRODUCT
 APPROVALS, KEY PLANS AND INSTALLATION SCHEDULES.
 SPECIFY THE MOUNTING TYPE, THE FASTENER TYPE, FASTENER
 SPACING, GLASS SEPARATION, EDGE DISTANCE, ETC. RULE
 9B-72
  
 7) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION. FBC 13-101.2.2
  
 8) SPECIFY THE TYPE OF TERMITE PROTECTION THAT WILL BE
 PROVIDED AS REQUIRED BY FBC R320.
  
 9) SHOW COMPLIANCE WITH FBC R704 INSPECTION FOR
 TERMITES, WHICH REQUIRES NOT LESS THAN 6" CLEARANCE
 BETWEEN EXTERIOR WALL COVERINGS AND FINAL EARTH GRADE
 AND A 4" SPACE ABOVE PATIO AND GARAGE SLABS AND ENTRY
 AREAS. NOTE: R 403.1.4 REQUIRES THE BOTTOM OF FOOTINGS
 TO BE A MINIMUM OF 12" BELOW GRADE. THEREFORE, AN 18"
 DEEP FOOTING IS REQUIRED TO ACHIEVE THE 6" CLEARANCE
 SITED ABOVE.
  
 10) SPECIFY THE TRUSS TO WALL CONNECTORS AND THE WALL
 STUD TO TOP PLATE CONNECTORS. R601.2 A CONTINUOUS LOAD
 PATH IS REQUIRED.
  
 11) THE ROOF NOTES ON A05 AND A06 SPECIFY THE SHEATHING
 FASTENER SPACING AS 4" O.C. AND THE SPACING IS GIVEN AS
 6" O.C. ON A07. PLEASE COORDINATE THE NOTES.
  
 12) SPECIFY THE SIZE AND TYPE OF WOOD THAT WILL BE USED
 FOR THE PORCH COLUMNS ON A08.
  
 13) ON A08 A CB66 CONNECTOR FOR A 6 X 6 WOOD POST IS
 SPECIFIED AT THE COLUMN BASE AND A CC 5-1/4 - 8 FOR A 8
 X 8 WOOD POST IS SPECIFIED FOR THE COLUMN CAP. PLEASE
 CLARIFY.
  
 14) ON A06 THE WOOD BEAM IS SPECIFIED AS (3) 3 X 12. IS
 THIS CORRECT OR SHOULD IT BE (3) 2 X 12 ?
  
 15) ON THE WALL SECTIONS ON A07 AND A08, THE INSULATION
 IS SPECIFIED AS R-11. THE MINIMUM INSULATION FOR 2 X 6
 FRAME WALLS IS R-13. FBC N1102
  
 NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE FENCE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW