Plan Review Notes For Permit 09060190
Permit Number 09060190
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-18 11:39:21REDLINED MAY NOT USE RISER TO SUPPORT CONDUCTORS.
 ALSO VIF EQUIPMENT GROUNDING PATH AS RISER SHOWS 3-3/0
 IN 1 1/2 CONDUIT.
 NO EQUIPMENT GROUNDING CONDUCTOR SHOWN. CONNECTORS/
 COUPLINGS APPROVED FOR EQUIPMENT GROUNDING PATH OR
 EQUIPMENT GROUNDING CONDUCTOR REQUIRED.