| Plan Review Notes For Permit 09060190 |
| Permit Number |
09060190 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-18 11:39:21 | REDLINED MAY NOT USE RISER TO SUPPORT CONDUCTORS. | | | ALSO VIF EQUIPMENT GROUNDING PATH AS RISER SHOWS 3-3/0 | | | IN 1 1/2 CONDUIT. | | | NO EQUIPMENT GROUNDING CONDUCTOR SHOWN. CONNECTORS/ | | | COUPLINGS APPROVED FOR EQUIPMENT GROUNDING PATH OR | | | EQUIPMENT GROUNDING CONDUCTOR REQUIRED. |
|