| 2009-11-03 08:37:09 | REVISED M1 DELTA 4, M2 DELTA 1. SEE PROVISO - M1 | | | | | | **PROVISO** | | | WALL ADJACENT TO STORAGE ROOM 106 IS SHOWN ON PAGE A1.1 | | | AS BEING 1-HOUR RATED. REVISE PAGE M1 TO SHOW THE DUCT | | | PENETRATIONS IN THIS WALL TO BE PROTECTED WITH FIRE | | | DAMPERS IN ACCORDANCE WITH FBC-M 607.5 AND FBC-M 607.8. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|