2009-09-24 08:56:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE PROVIDE INFORMATION REGARDING THE WATER
 CURTAIN. IT IS NOT CLEAR HOW THIS WILL WORK PROPERLY AS
 DESIGNED; ISN'T THE WATER TO HIT THE WALL ABOVE THE
 WINDOW AND THEN RUN DOWN THE WINDOW, WITH MULLIONS ON
 THE WINDOW PROHIBITED? A BULKHEAD ABOVE THE DOOR/WINDOW
 HAS BEEN PROPOSED, SO IT IS NOT CLEAR HOW THE WATER
 CURTAIN ON EITHER SIDE WILL WORK. PROVIDE SPECIFICATION
 SHEETS FOR THE SPRINKLER HEADS, DIMENSION FOR THE
 BULKHEAD, AND ANY OTHER INFORMATION REQUIRED TO
 DEMONSTRATE COMPLIANCE WITH FBC715.4. ALSO, PLEASE NOTE
 DISTANCE FROM THE PROPOSED WATER CURTAIN SPRINKLER
 HEADS TO THE EXISTING FIRE SPRINKLERS IN THE CORRIDOR.
 THIS INFORMATION IS TO BE EITHER PREPARED BY THE FIRE
 SPRINKLER ENGINEER OR REVIEWED BY THE FIRE SPRINKLER
 ENGINEER.
  
  