| 2009-07-09 13:06:26 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLAN SHOWS WHAT APPEARS TO BE TWO FIRE DAMPERS AT | | | THE SUPPLY AND RETURN DUCT PENETRATIONS FOR EXISTING | | | UNIT EM07 BUT THEY ARE NOT LABELED ON THE PLANS. PLEASE | | | IDENTIFY THESE LOCATIONS AND INDICATE WHETHER THESE ARE | | | NEW OR EXISTING DAMPERS IN ACCORDANCE WITH FBC-M 607.8. | | | | | | 2. PAGE M-2 SHOWS A DETAIL FOR MOTORIZED VOLUME DAMPER | | | LOCATION AND SEQUENCE FOR THE BUILDING SMOKE CONTROL | | | SYSTEM. THESE DAMPERS AND ASSOCIATED DUCTS DO NOT | | | APPEAR ON FLOOR PLANS. PLEASE COORDINATE FLOOR PLANS | | | WITH DETAIL AND SEQUENCE TO SHOW COMPLIANCE WITH FBC-M | | | SECTION 513. | | | | | | 3. EXISTING UNIT EM07 SHARES A COMMON RETURN AIR PLENUM | | | WITH OTHER UNITS IN THE CONFERENCE AREA. WHERE MULTIPLE | | | AIR-HANDLING SYSTEMS SHARE COMMON PLENUMS WITH A | | | COMBINED DESIGN CAPACITY GREATER THAN 2,000 CFM,EACH | | | UNIT SHALL BE PROVIDED WITH SMOKE DETECTORS IN | | | ACCORDANCE WITH FBC-M 606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|