2009-07-09 13:06:26REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLAN SHOWS WHAT APPEARS TO BE TWO FIRE DAMPERS AT
 THE SUPPLY AND RETURN DUCT PENETRATIONS FOR EXISTING
 UNIT EM07 BUT THEY ARE NOT LABELED ON THE PLANS. PLEASE
 IDENTIFY THESE LOCATIONS AND INDICATE WHETHER THESE ARE
 NEW OR EXISTING DAMPERS IN ACCORDANCE WITH FBC-M 607.8.
  
 2. PAGE M-2 SHOWS A DETAIL FOR MOTORIZED VOLUME DAMPER
 LOCATION AND SEQUENCE FOR THE BUILDING SMOKE CONTROL
 SYSTEM. THESE DAMPERS AND ASSOCIATED DUCTS DO NOT
 APPEAR ON FLOOR PLANS. PLEASE COORDINATE FLOOR PLANS
 WITH DETAIL AND SEQUENCE TO SHOW COMPLIANCE WITH FBC-M
 SECTION 513.
  
 3. EXISTING UNIT EM07 SHARES A COMMON RETURN AIR PLENUM
 WITH OTHER UNITS IN THE CONFERENCE AREA. WHERE MULTIPLE
 AIR-HANDLING SYSTEMS SHARE COMMON PLENUMS WITH A
 COMBINED DESIGN CAPACITY GREATER THAN 2,000 CFM,EACH
 UNIT SHALL BE PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH FBC-M 606.2.1.
  