| Plan Review Notes For Permit 09060185 |
| Permit Number |
09060185 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-30 11:04:30 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. ON SHEET A3.1, GENERAL NOTE #8 AND #9 REFERENCES | | | FLORIDA FIRE PREVENTION CODE - 2004 EDITION. CORRELATE | | | TO CURRENT EDITION AS CORRECTLY SHOWN ON SHEET T UNDER | | | CODES. | | | | | | 3. ON SHEET A3.1, THE NEW FIRE RATED DOOR (DOOR A) | | | SHALL BE 20 MINUTES. | | | | | | 4. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE SPRINKLER | | | HEADS TO BE REMODELED IN ANY MANNER? IF SO, PROVIDE A | | | LAYOUT OF THE FIRE SPRINKLER. (THEY MAY BE SHOWN ON | | | SHEET A2.1, REFLECTED CEILING PLAN). | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|