Plan Review Notes For Permit 09060185
Permit Number 09060185
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-06-30 11:04:30*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. ON SHEET A3.1, GENERAL NOTE #8 AND #9 REFERENCES
 FLORIDA FIRE PREVENTION CODE - 2004 EDITION. CORRELATE
 TO CURRENT EDITION AS CORRECTLY SHOWN ON SHEET T UNDER
 CODES.
  
 3. ON SHEET A3.1, THE NEW FIRE RATED DOOR (DOOR A)
 SHALL BE 20 MINUTES.
  
 4. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE SPRINKLER
 HEADS TO BE REMODELED IN ANY MANNER? IF SO, PROVIDE A
 LAYOUT OF THE FIRE SPRINKLER. (THEY MAY BE SHOWN ON
 SHEET A2.1, REFLECTED CEILING PLAN).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722