Plan Review Notes
Plan Review Notes For Permit 09060185
Permit Number 09060185
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-03 09:30:42** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
  
  
 2) NOTE: THE PANEL AND TRANSFORMER LOCATION NEEDS TO BE
 IDENTIFIED AS ELECTRICAL ROOM. PLEASE ALSO NOTE THAT
 SIGNAGE WILL BE REQUIRED FOR ELECTRICAL ROOM, NO
 STORAGE OR WORDS TO THAT AFFECT.
 110.26, 240.24
  
 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE 13-415.AB.5. PLANS STATE TO SEE DOCUMENTS
 ATTACHED. THE ATTACHED CALCULATIONS ARE COMCHECK
 SOFTWARE WHICH IS NOT ADOPTED BY THE STATE OF FLORIDA.
 PLEASE SEE 13-400 AS THE ONLY ADOPTED PROGRAM IS
 FLA-COM.
 PLEASE BE SURE THE RESPONSIBLE DESIGN PROFESSIONAL
 UNDER FBC 13-101, 103, FS 471,481.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  