2009-07-03 09:26:31 
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
  
 2) NOTE: PLEASE SEE 210.8B2 FOR ALL RECEPTACLES IN
 KITCHEN AREAS TO BE GFI OR GFI PROTECTED WHETHER OR NOT
 THEY SERVE COUNTER SPACES. THE CODE WAS REVISED THAT IT
 IS NO LONGER ONLY RECEPTACLES WITHIN 6FT OF SINKS. THIS
 WOULD INCLUDE AREAS WHERE KITCHEN EQUIPMENT SUCH AS ICE
 MACHINES, DISHWASHERS AND OTHER SERVICE EQUIPMENT IS
 LOCATED. AREAS WHERE FLOORS ETC ARE WET IS A HIGH AREA
 OF HAZARD IN KITCHENS IN COMMERCIAL LOCATIONS. PLEASE
 SEE COMMENTARY IN THE 2005 NEC.
  
 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE 13-415.AB.5. IS THERE OTHER EXISTING LIGHTING?
  
 5) NOTE: PLEASE SHOW LIGHTING PER NFPA-101 7.8,
 7.9.2.1,.2.2. NO BATTERY BACK UP FIXTURES SHOWN FOR
 MINIMUM EGRESS LIGHTING.
 ** PLEASE KEEP IN MIND THE BUILDING SHALL NOT BE
 OCCUPIED UNDER EMERGENCY POWER. IF OCCUPIED UNDER
 EMERGENCY POWER IF THE GENERATOR BREAKER IS TRIPPED OR
 LOST THEN NO EGRESS LIGHTING WOULD BE PROVIDED. THIS
 COULD LEAVE LIFE SAFETY EGRESS AREAS IN TOTAL DARKNESS.
 PLEASE BE SURE TO GO OVER THIS WITH BUILDING
 OWNER/MANAGEMENT.
 OBTAIN IN WRITING THAT BUILDING SHALL NOT BE OCCUPIED
 UNDER EMERGENCY POWER.
  
 6) NOTE: PLEASE INDICATE THE REQUIRED LIGHTING CONTROLS
 PER FBC 13-415.AB.1,.1.2, .1.3. SOME ARE SHOWN ON PLANS
 HOWEVER NOT ALL. SEE AREAS 200,201, ONLY WHAT APPEARS
 AS A SINGLE POLE SWITCH IS SHOWN. AS THE SYMBOL LEGEND
 DOES NOT INCLUDE THIS DEVICE IT IS UNCLEAR AT THIS
 TIME. OTHER AREAS IN THE BACK OF HOUSE DO SHOW THE
 REQUIRED CONTROLS.
  
 7) NOTE: PLEASE SEE 422.13, WATER HEATER LOAD IS
 CONSIDERED CONTINUOUS WHICH REQUIRES THIS TO BE FIGURED
 AT 125%.
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  