| Plan Review Notes For Permit 09060182 |
| Permit Number |
09060182 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-06-23 07:33:25 | BUILDING PROVISO: | | | SUBMIT FLOOR INSULATION TYPE BEFORE INSPECTION: | | | 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES | | | BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A | | | PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE | | | AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS | | | THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE | | | WITH ASTM E 492. | | | | | | |
|