Plan Review Notes
Plan Review Notes For Permit 09060170
Permit Number 09060170
Review Stop P
Sequence Number 1
Notes
Date Text
2009-07-02 09:57:37 
  
  
 PASSED/PROVISO:
  
 A REVISION IS REQUIRED SHOWING COMPLIANCE WITH THE
 FOLLOWING:
  
 SHT A-1 GEN. PLMG NOTES #1 DELETE REFERENCE TO
 FBC-2004. SECTION 110.1.2.
 SHT A-1 SHOW CLEAR FLOOR SPACE FOR BREAK ROOM SINK.
 SECTION 11-4.24.5
 SHT A-3 WALL SECTION-2 INDICATE THE SIZE OF THE SCUPPER
 OPENINGS, THE RAINWATER COLLECTOR BOXES & RAINWATER
 LEADERS. TABLE 1106.3
 SUBMIT A DETAIL FOR THE OVERFLOW SCUPPERS SHOWING THE
 WIDTH & HEIGHT AND INDICATE THE DISTANCE FROM THE ROOF
 TO THE FLOW LINE OF THE O/F SCUPPER. SECTION 1503.4.3
  
  
  
  
 .