| Plan Review Notes For Permit 09060170 |
| Permit Number |
09060170 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-02 09:57:37 | | | | | | | | | | PASSED/PROVISO: | | | | | | A REVISION IS REQUIRED SHOWING COMPLIANCE WITH THE | | | FOLLOWING: | | | | | | SHT A-1 GEN. PLMG NOTES #1 DELETE REFERENCE TO | | | FBC-2004. SECTION 110.1.2. | | | SHT A-1 SHOW CLEAR FLOOR SPACE FOR BREAK ROOM SINK. | | | SECTION 11-4.24.5 | | | SHT A-3 WALL SECTION-2 INDICATE THE SIZE OF THE SCUPPER | | | OPENINGS, THE RAINWATER COLLECTOR BOXES & RAINWATER | | | LEADERS. TABLE 1106.3 | | | SUBMIT A DETAIL FOR THE OVERFLOW SCUPPERS SHOWING THE | | | WIDTH & HEIGHT AND INDICATE THE DISTANCE FROM THE ROOF | | | TO THE FLOW LINE OF THE O/F SCUPPER. SECTION 1503.4.3 | | | | | | | | | | | | | | | . |
|