Plan Review Notes
Plan Review Notes For Permit 09060170
Permit Number 09060170
Review Stop M
Sequence Number 1
Notes
Date Text
2009-07-22 16:13:19REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
  
 1. PROVIDE DUCT SMOKE DETECTOR ON RTU-2 AND RTU-4 IN
 ACCORDANCE WITH FBC-M 606.2.1.
  
 2. PAGE M-2 HAS ATTACHMENT DETAILS FOR CURB AND RTU.
 THE SPECIFIED YORK PACKAGE UNITS HAVE MANUFACTURER
 SUPPLIED WIND RESISTANCE CERTIFICATION WITH REQUIRED
 INSTALLATION KIT AND INSTALLATION INSTRUCTIONS. THE
 MANUFACTURERS PRODUCT AND MOUNTING CERTIFICATION SHALL
 BE USED FOR ATTACHMENT TO BUILDING STRUCTURE IN ORDER
 FOR THE WIND CERTIFICATION TO BE VALID AND DEMONSTRATE
 COMPLIANCE WITH FBC-M 301.12. PROVIDE SUPPORTING
 DOCUMENTATION AS PART OF THE PERMIT PACKAGE.
  
 3. PLEASE SHOW THE TERMNATION LOCATION OF EXHAUST
 OUTLETS FOR RESTROOMS 102 AND 103 IN ACCORDANCE WITH
 FBC-M 401.4 AND FBC-M 501.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]