| 2009-07-23 14:07:43 | *****DENIED***** |
| | |
| | |
| | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. |
| | |
| | 2. EFFECTIVE 12/31/2008, THE 2007 EDITION OF FLORIDA |
| | FIRE PREVENTION CODE BASED ON NFPA 1, UNIFORM FIRE |
| | CODE, 2006 EDITION AND NFPA 101, LIFE SAFETY CODE, 2006 |
| | EDITION SHALL BE REFERENCED. |
| | |
| | 3. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN |
| | UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 |
| | FEET 6 INCHES. MINIMUM WIDTH (SEE SHEET A-0) MAY BE |
| | REDUCED TO MEET SPECIAL ACCESS WITH THE APPROVAL OF THE |
| | FIRE OFFICIAL. |
| | |
| | 4. IN THE DESIGN CRITERIA ON SHEET A-1, THE OCCUPANT |
| | LOAD FOR MERCANTILE IS LISTED AS 60 SF PER PERSON. AS |
| | PER NFPA 101, SALES AREA ON THE STREET FLOOR IS 30 SF |
| | PER PERSON. |
| | |
| | 5. ON THE ELEVATION WHICH FRONTS PALM BEACH LAKES |
| | BOULEVARD, DISPLAY/SHOW THE NUMERICAL ADDRESS ON THE |
| | BUILDING. AS PER WEST PALM BEACH CODE, THE NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" |
| | IN WIDTH/STROKE. |
| | |
| | 6. SINCE THERE ARE TWO TENANT SPACES FOR THE SAME |
| | ADDRESS, HOW WILL THEY BE DESIGNATED FRON ONE ANOTHER? |
| | |
| | 7. INDISCREPANCIES SHOWN IN THE DOOR SCHEDULE AS LISTED |
| | ON SHEET A-4. FOR EXAMPLE, DOOR 118A IS LISTED AS AN |
| | "EXISTING GARAGE DOOR TO BE USED" AND DOOR 119A AS A |
| | "METAL EXTERIOR DOOR W/ WEATHER STRIPPING" . |
| | |
| | 8. SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 9. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHERS WHICH SATIFY THE 75' TRAVEL DISTANCE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |