| 2009-06-25 13:38:15 | |
| | |
| | |
| | |
| | |
| | |
| | ** DENIED PLANS ** |
| | |
| | *** IT IS IMPORTANT TO KNOW THAT THERE IS INFORMATION |
| | NOT YET SHOWN OR SUBMITTED FOR REVIEW OF MINIMUM CODE |
| | COMPLIANCE. THEREFORE THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THE VALUE FOR THE COMPLETE SCOPE |
| | OF WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT |
| | WHICH IS PERMANENTLY INSTALLED AND DESIGN COST. EVEN IF |
| | ANY OF THESE ARE OWNER SUPPLIED. THE VALUE HAS BEEN |
| | ADJUSTED FOR THE BASE BUILDING PER THE ICC TABLES FOR |
| | TYPE III-B CONSTRUCTION. THE SQ FT FOR MEDICAL OFFICE |
| | AND MERCANTILE WERE BOTH FIGURED SEPARATE. |
| | THE VALUE IS STILL TO BE BASED ON NOTES ABOVE. THE |
| | ADJUSTED VALUE DOES NOT INCLUDE ANY SPECIALIZED |
| | EQUIPMENT. |
| | FBC 108.3 |
| | |
| | 2) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES AS WELL |
| | AS BUILDING REVIEW COMMENTS WHICH WILL BE FORTHCOMING. |
| | |
| | 3) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING |
| | CODES AT A MINIMUM. SOME ARE CURRENT AND OK HOWEVER |
| | SOME NOTED ON SOME SHEETS ARE CODES WHICH ARE NO LONGER |
| | ADOPTED. |
| | |
| | 2007 FBC W/ 2009 REVISIONS |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | 2002 NFPA-72 ( WHEN APPLICABLE. |
| | 2007 FLORIDA FIRE PREVENTION CODE. ( INCORRECT EDITION |
| | SHOWN). |
| | 2006 NFPA-1 |
| | |
| | |
| | 4) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS IN |
| | COMPLIANCE WITH CHAPTER 13 OF THE FBC. PLEASE SEE SOME |
| | EXAMPLES WHICH WILL BE GIVEN BELOW. THESE ARE NOT ALL |
| | POSSIBLE ITEMS AS THERE WILL BE COMMENTS FROM OTHER |
| | TRADES. |
| | FOR EXAMPLE: THERE IS ELECTRIC WATER HEATER YET THE |
| | PIPING FOR HOT WATER IS SHOWN BLANK IN THE INPUT DATA |
| | REPORT. THIS IS NOT POSSIBLE WHEN SECTION 13-411.AB.2 |
| | FOR EXAMPLE: PLEASE SEE ITEMS SUCH THE PENDANT LIGHT(S) |
| | WHICH ARE MISSING FROM IDR. |
| | 13-415.AB.5 |
| | |
| | 5) NOTE: PLEASE PROVIDE INFORMATION FOR THE REQUIRED |
| | ASTRONOMICAL TIME CLOCK AND HOURS OF BACK UP PER |
| | 13-415.AB.1.4. THE PLANS MENTION A TIME CLOCK HOWEVER |
| | NOT OF THE REQUIRED TYPE AND BACK UP. |
| | |
| | 6) NOTE: PLEASE PLACE NOTES ON PLANS SPECIFIC TO NEC |
| | 517 PART II (TWO). REDUNDANT GROUNDING IS REQUIRED. |
| | |
| | 7) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY |
| | AND EXIT LIGHTS. |
| | |
| | 8) NOTE: PLEASE EXPLAIN THE METHOD OF LIGHTING CONTROLS |
| | SHOWN. |
| | |
| | 9) NOTE: THE PLANS MAKE NOTE OF THE GENERATOR AS FUTURE |
| | HOWEVER PLEASE SEE POSSIBLE NOTES FOR SITE PLAN |
| | APPROVAL. PLEASE ALSO BE AWARE OF LOCATION FOR ALL |
| | CLEARANCES AND REQUIREMENTS FOR ALL TRADES. ATTENTION |
| | TO CODES FOR GENERATOR INSTALLATION ALSO NEEDS TO BE |
| | LOOKED AT AHEAD OF TIME FOR LOCATION ETC. |
| | |
| | 10) NOTE: PLANS MENTIONS TRANSFORMERS ARE TO BE LOCATED |
| | ON THE OUTSIDE OF THE BUILDING WHERE THERE IS ONLY FIVE |
| | FEET OF SPACE. PLEASE PROVIDE A COMPLETE LAYOUT FOR |
| | SIZE OF UNITS, MOUNTING, ACCESS AND CLEARANCE |
| | REQUIREMENTS. |
| | 110.26, 450.9 ETC |
| | |
| | 11) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT |
| | SHEETS ON THE PROPOSED SE RATED ATS. 90.7,110.3, 230.70 |
| | ETC |
| | |
| | 12) NOTE: PLEASE CONTACT SERVICE PLANNER FOR THE |
| | LOCATION OF METERING DEVICES. AS SHOWN FPL WOULD BILL |
| | THE OWNER FOR ALL POWER DERIVED FROM THE GENERATOR. |
| | |
| | 13) NOTE: PLEASE COORDINATE RISER AND PANELS. THE RISER |
| | DOES NOT SHOW ANY MDP. 215.5, 240,310,230 ETC |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |