2009-06-25 13:38:15 
  
  
  
  
  
 ** DENIED PLANS **
  
 *** IT IS IMPORTANT TO KNOW THAT THERE IS INFORMATION
 NOT YET SHOWN OR SUBMITTED FOR REVIEW OF MINIMUM CODE
 COMPLIANCE. THEREFORE THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
 1) NOTE: PLEASE KNOW THE VALUE FOR THE COMPLETE SCOPE
 OF WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT
 WHICH IS PERMANENTLY INSTALLED AND DESIGN COST. EVEN IF
 ANY OF THESE ARE OWNER SUPPLIED. THE VALUE HAS BEEN
 ADJUSTED FOR THE BASE BUILDING PER THE ICC TABLES FOR
 TYPE III-B CONSTRUCTION. THE SQ FT FOR MEDICAL OFFICE
 AND MERCANTILE WERE BOTH FIGURED SEPARATE.
 THE VALUE IS STILL TO BE BASED ON NOTES ABOVE. THE
 ADJUSTED VALUE DOES NOT INCLUDE ANY SPECIALIZED
 EQUIPMENT.
 FBC 108.3
  
 2) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES AS WELL
 AS BUILDING REVIEW COMMENTS WHICH WILL BE FORTHCOMING.
  
 3) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 CODES AT A MINIMUM. SOME ARE CURRENT AND OK HOWEVER
 SOME NOTED ON SOME SHEETS ARE CODES WHICH ARE NO LONGER
 ADOPTED.
  
 2007 FBC W/ 2009 REVISIONS
 2005 NFPA-70
 2006 NFPA-101
 2002 NFPA-72 ( WHEN APPLICABLE.
 2007 FLORIDA FIRE PREVENTION CODE. ( INCORRECT EDITION
 SHOWN).
 2006 NFPA-1
  
  
 4) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS IN
 COMPLIANCE WITH CHAPTER 13 OF THE FBC. PLEASE SEE SOME
 EXAMPLES WHICH WILL BE GIVEN BELOW. THESE ARE NOT ALL
 POSSIBLE ITEMS AS THERE WILL BE COMMENTS FROM OTHER
 TRADES.
 FOR EXAMPLE: THERE IS ELECTRIC WATER HEATER YET THE
 PIPING FOR HOT WATER IS SHOWN BLANK IN THE INPUT DATA
 REPORT. THIS IS NOT POSSIBLE WHEN SECTION 13-411.AB.2
 FOR EXAMPLE: PLEASE SEE ITEMS SUCH THE PENDANT LIGHT(S)
 WHICH ARE MISSING FROM IDR.
 13-415.AB.5
  
 5) NOTE: PLEASE PROVIDE INFORMATION FOR THE REQUIRED
 ASTRONOMICAL TIME CLOCK AND HOURS OF BACK UP PER
 13-415.AB.1.4. THE PLANS MENTION A TIME CLOCK HOWEVER
 NOT OF THE REQUIRED TYPE AND BACK UP.
  
 6) NOTE: PLEASE PLACE NOTES ON PLANS SPECIFIC TO NEC
 517 PART II (TWO). REDUNDANT GROUNDING IS REQUIRED.
  
 7) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS.
  
 8) NOTE: PLEASE EXPLAIN THE METHOD OF LIGHTING CONTROLS
 SHOWN.
  
 9) NOTE: THE PLANS MAKE NOTE OF THE GENERATOR AS FUTURE
 HOWEVER PLEASE SEE POSSIBLE NOTES FOR SITE PLAN
 APPROVAL. PLEASE ALSO BE AWARE OF LOCATION FOR ALL
 CLEARANCES AND REQUIREMENTS FOR ALL TRADES. ATTENTION
 TO CODES FOR GENERATOR INSTALLATION ALSO NEEDS TO BE
 LOOKED AT AHEAD OF TIME FOR LOCATION ETC.
  
 10) NOTE: PLANS MENTIONS TRANSFORMERS ARE TO BE LOCATED
 ON THE OUTSIDE OF THE BUILDING WHERE THERE IS ONLY FIVE
 FEET OF SPACE. PLEASE PROVIDE A COMPLETE LAYOUT FOR
 SIZE OF UNITS, MOUNTING, ACCESS AND CLEARANCE
 REQUIREMENTS.
 110.26, 450.9 ETC
  
 11) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT
 SHEETS ON THE PROPOSED SE RATED ATS. 90.7,110.3, 230.70
 ETC
  
 12) NOTE: PLEASE CONTACT SERVICE PLANNER FOR THE
 LOCATION OF METERING DEVICES. AS SHOWN FPL WOULD BILL
 THE OWNER FOR ALL POWER DERIVED FROM THE GENERATOR.
  
 13) NOTE: PLEASE COORDINATE RISER AND PANELS. THE RISER
 DOES NOT SHOW ANY MDP. 215.5, 240,310,230 ETC
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  