| 2009-06-22 13:34:18 | BUILDING PLAN REVIEW |
| | PERMIT: 09060170 |
| | ADD: PALM BEACH LAKES BLVD |
| | CONT: DREAM BUILDERS |
| | TEL: (561)716-1291 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. |
| | |
| | B) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | (1) SITE PLAN IS MISSING REQUIREMENTS FOR THE |
| | HANDICAPPED PARKING AND ACCESS AISLE IN REGARDS TO |
| | CHANGE IN GRADE. PARKING SPACES AND ACCESS AISLES SHALL |
| | BE LEVEL WITH SURFACE |
| | SLOPES NOT EXCEEDING 1:50 (2 PERCENT) IN ALL DIRECTIONS |
| | (11-4.6.3). |
| | |
| | (2) SITE PLAN IS MISSING INFORMATION ON 11-4.29.5 |
| | DETECTABLE WARNINGS AT HAZARDOUS VEHICULAR AREAS. IF A |
| | WALK CROSSES OR ADJOINS A VEHICULAR WAY, AND THE |
| | WALKING SURFACES ARE NOT |
| | SEPARATED BY CURBS, RAILINGS, OR OTHER ELEMENTS BETWEEN |
| | THE PEDESTRIAN AREAS AND VEHICULAR AREAS, THE BOUNDARY |
| | BETWEEN THE AREAS SHALL BE DEFINED BY A CONTINUOUS |
| | DETECTABLE |
| | WARNING WHICH IS 36 INCHES (915 MM) WIDE, COMPLYING |
| | WITH SECTION 11-4.29.2. |
| | |
| | (3) SITE PLAN DOES NOT INDICATE IF THERE IS A CURB CUT |
| | FOR A CURB RAMP MAY REQUIRE: 11-4.7 CURB RAMPS. |
| | 11-4.7.1 LOCATION. CURB RAMPS COMPLYING WITH SECTION |
| | 11-4.7 SHALL BE PROVIDED |
| | WHEREVER AN ACCESSIBLE ROUTE CROSSES A CURB. |
| | |
| | (4) 11-4. 1.2(5)(D) AT FACILITIES PROVIDING MEDICAL |
| | CARE AND OTHER SERVICES FOR PERSONS WITH MOBILITY |
| | IMPAIRMENTS, PARKING SPACES COMPLYING WITH SECTION |
| | 11-4.6 SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION 11-4.1.2(5)(A) EXCEPT AS |
| | FOLLOWS: |
| | (I) OUTPATIENT UNITS AND FACILITIES: 10 PERCENT OF THE |
| | TOTAL NUMBER OF PARKING SPACES PROVIDED SERVING EACH |
| | SUCH OUTPATIENT UNIT OR FACILITY; |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME BECAUSE |
| | OF THE MISSING SITE PLAN, AS A RESULT OF THE ADDITIONAL |
| | INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR |
| | THAT WERE NOT PART OF THIS REVIEW. |
| | |
| | |
| | 2) BOTH SHEETS A0 & A1 BOTH INDICATE THIS BUILDING TO |
| | BE DESIGNED AS A TYPE 3-B CONSTRUCTION, PLEASE PROVIDE |
| | DOCUMENTATION FOR 2 HOUR EXTERIOR BEARING WALL (REAR |
| | WALL) AS REQUIRED BY TABLE 602. PROVIDE FROM THE BLOCK |
| | MANUFACTURER THE EQUIVALENT THICKNESS FOR A 2HR RATED |
| | CONCRETE BLOCK. SECTION 721.3.1 EQUIVALENT THICKNESS. |
| | TABLE 721.3.2. |
| | |
| | 3) PLEASE ALSO REVIEW THE REQUIREMENTS OF TABLE 704.8 |
| | FOR ALLOWABLE PERCEENTAGE OF UNPROTECTED OPENINGS. |
| | CURRENTLY THE PLANS INDICATE THE REAR WALL LINE AT |
| | 5'-0". THE TABLE INDICATES FOR UNPROTECTED OPENINGS 3' |
| | TO 5'-0" OPENINGS ARE NOT PROMITTED. GREATER THAN 5'-0" |
| | TO 10'-0" TTHE AMOUNT WOULD BE 10% ALSO REVIEW FOOTNOTE |
| | "I". PLEASE UPDATE PLANS ACCORDINGLY. |
| | |
| | 4) SHEET A1 DOOR #101B IS MISSING THE REQUIRED 18" |
| | LATCH SIDE. 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT |
| | AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE CLEAR & LEVEL. |
| | |
| | 5) SHEET A1 AND SHEET A4 DOOR SCHEDULE INDICATE THESE |
| | DOORS (116B, 118A, 120A, 121A, 124B, 125A & 129A) NOT |
| | IN COMPLIANCE WITH : 11-4.13.5 DOORWAY MIN CLEAR WIDTH |
| | . DOORWAYS SHALL HAVE A MINIMUM CLEAR WIDTH OF 32" WITH |
| | THE DOOR OPEN 90-DEGREES, MEASURED BETWEEN THE FACE OF |
| | THE DOOR AND OPPOSITE STOP. |
| | |
| | 6) SHEET A1 DOOR# 120A AND DOOR# 121A WHEN REVISED TO |
| | EITHER A 34" OR 36" DOOR WILL NOT MEET THE REQUIREMENTS |
| | OF 1008.1.8.8 DURING ITS SWING, ANY DOOR IN A MEANS OF |
| | EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF |
| | THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR |
| | LANDING, NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO |
| | THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR |
| | LANDING, WHEN FULLY OPEN. |
| | |
| | 7) ROOM 118 X-RAY ROOM AND 124 CT SCAN ROOMS BOTH |
| | INDICATE THE USE OF LEAD LINED WALLS. PLEASE INDICATE |
| | COMPLIANCE WITH: |
| | 435.5.1 SHIELDING. EACH X-RAY FACILITY SHALL HAVE |
| | PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS NEEDED TO |
| | ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A RADIATION |
| | DOSE IN EXCESS OF THE LIMITS SPECIFIED IN PART III OF |
| | CHAPTER 64 E-5, FLORIDA ADMINISTRATIVE CODE . CONTACT: |
| | TOM TOMCZAK (904) 278-5730 |
| | 705 ROSE RD SUITE# 300 |
| | ORANGE PARK, FL 32073 |
| | |
| | 435.5.1.1 |
| | STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL |
| | BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND |
| | WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7 |
| | FEET (2.1 M). |
| | 435.5.1.2 |
| | DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL |
| | HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT |
| | REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE |
| | INSTALLED. |
| | 435.5.1.3 PLEASE NOTE A-4 DOOR# 116B IS INDICATED AS A |
| | D3 ALUMINUM DOUBLE DOOR, GLASS. |
| | PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT |
| | ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS |
| | OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF |
| | 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC |
| | PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH |
| | FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE |
| | BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, |
| | USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR |
| | RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN |
| | INTO CONSIDERATION. |
| | 435.5.1.3.1 |
| | THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING: |
| | 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S |
| | RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS; |
| | GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY |
| | WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S |
| | BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL. |
| | 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS |
| | OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS, |
| | FLOOR AND CEILING OF THE ROOM CONCERNED. 435.5.1.3.1.3 |
| | THE DIMENSIONS OF THE ROOM CONCERNED. 435.5.1.3.1.4 THE |
| | TYPE OF OCCUPANCY OF ALL ADJACENT AREAS INCLUSIVE OF |
| | SPACE ABOVE AND BELOW THE ROOM CONCERNED. IF THERE IS |
| | AN EXTERIOR WALL, THE DISTANCE TO THE CLOSEST AREA |
| | WHERE IT IS LIKELY THAT INDIVIDUALS MAY BE PRESENT. |
| | 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT |
| | AND THE MAXIMUM TECHNIQUE FACTORS. |
| | 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS |
| | WHICH WILL BE PERFORMED WITH THE EQUIPMENT. |
| | |
| | 8) SHEET A1 INDICATES WHAT APPEARS TO BE A BLOCK WALL |
| | SEPERATING THE TO TENANTS. 708.1(7) REQUIRES THIS TO BE |
| | A FIRE RATED PARTITION. 708.3 REQUIRES IT TO BE A 1 HR |
| | FIRE RATED PARTITION.PLEASE INDICATE AS SUCH AND ALSO |
| | PROVIDE CONTINUITY TO THE ROOF DECK ABOVE. 708.4 |
| | CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE TOP |
| | OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO |
| | THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR |
| | DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED |
| | FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL |
| | BE SECURELY ATTACHED THERETO. IF THE PARTITIONS ARE NOT |
| | CONTINUOUS TO THE SHEATHING, DECK OR SLAB, AND WHERE |
| | CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION, THE SPACE |
| | BETWEEN THE CEILING AND THE SHEATHING, DECK OR SLAB |
| | ABOVE SHALL BE FIREBLOCKED OR DRAFTSTOPPED IN |
| | ACCORDANCE WITH SECTIONS 717.2 AND 717.3 AT THE |
| | PARTITION LINE. |
| | |
| | |
| | 9) SHEET A-2 INDICATES THE USE OF A FIXED LADDER,PLEASE |
| | PROVIDE MANUFACTURERS SPEC IN COMPLIANCE WITH: |
| | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| | ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| | CRITERIA: |
| | |
| | 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| | ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| | |
| | 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| | INCHES (356 MM) ON CENTER. |
| | |
| | 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6 |
| | INCHES (152 MM) DEEP. |
| | |
| | 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| | BETWEEN RAILS. |
| | |
| | 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| | DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| | (136.1 KG) LOAD. |
| | |
| | 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| | PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| | WITHSTANDING 100 POUNDS (488.2 KG/M2) PER SQUARE FOOT. |
| | |
| | 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| | APPROVED MEANS. |
| | |
| | 10) SHEET A-3 SECTION -2 IS A DETAIL FOR SCUPPERS, SIZE |
| | NOT PROVIDED, 1503.4.2.THE SCUPPER SHALL BE LOCATED AS |
| | DETERMINED BY THE SLOPE AND THE CONTRIBUTING AREA OF |
| | THE ROOF. |
| | |
| | 11) THE ELEVATION (A-2) INDICATE 7 SCUPPERS BUT ONLY 6 |
| | OVERFLOWS. 1503.4.3 OVERFLOW SCUPPERS. WHEN OTHER MEANS |
| | OF DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW |
| | SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS |
| | THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM) |
| | ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED |
| | AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR |
| | DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW |
| | SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, PLUMBING . |
| | |
| | 12) A/C CURB DETAIL FOR DOWN UNITS, SHEET A4 INDICATES |
| | THE USE OF 2 2X PT NAILERS TO THE METAL B-DECKING, THE |
| | A-4 INDICATES THE FASTENERS AS APPROVED FASTENERS AT 6 |
| | INCHES ON CENTER, S-DOES NOT PROVIDE THE ATTACHMENT |
| | INFORMATION WHEREAS M-2 INDICATES TTHE CURB TO BE |
| | ATTACHED BY WELDING TO ANGLE IRON, PLEASE CORRDINATE |
| | PLANS, 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 13) ROOFTOP EQUIPMENT WILL NEED TO MEET WIND LOADING AS |
| | REQUIRED BY CHAPTER 1609 FBC. 301.13 FBC MECHANICAL. |
| | WIND RESISTANCE. MECHANICAL EQUIPMENT, APPLIANCES AND |
| | SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| | INSTALLED TO RESIST WIND PRESSURES ON THE EQUIPMENT AND |
| | THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 14) DISCREPANCY BETWEEN S01 AND S1 FOR FOUNDATIONS. S01 |
| | INDICATES THE MINIMUM FOUNDATION VALUES TO BE 3000PSF |
| | WHEREAS S1 INDICATES A 2500 PSF. S1 ALSO INDICATES A |
| | SOILS TEST WAS COMPLETED OCT 4,2005 JOB# 05-21-5749. |
| | 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| | POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| | VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| | CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| | NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| | SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| | THROUGH 1802.6 . PLEASE PROVIDE ORIGINALS OF SIGNED AND |
| | SEALED SOILS REPORTS, NOT COPIES. |
| | |
| | 15) PRODUCT APPROVALS: |
| | |
| | 15A) PGT/ PW- 701AL FIXED WINDOW NOA 08-1112.10 |
| | THIS NOA IS FOR SINGLE FIXED FRAME WITH EITHER A |
| | INTEGRAL FIN FRAME OR FLANGED FIN FRAME. THIS NOA DOES |
| | NOT INDICATE THE USE OF MULLIONS AAS REQUIRED FOR |
| | WINDOW UNITS W-2 & W-3. |
| | |
| | 1714.5.5.1 MULLIONS. MULLIONS OR MULLED FENESTRATION |
| | ASSEMBLIES SHALL BE TESTED BY AN APPROVED TESTING |
| | LABORATORY IN ACCORDANCE WITH EITHER AAMA 450, ASTM E |
| | 330, OR TAS 202 (HVHZ SHALL COMPLY WITH TAS 202), OR |
| | SHALL BE ENGINEERED IN ACCORDANCE WITH AAMA 450 USING |
| | ACCEPTED ENGINEERING PRACTICE. MULLIONS TESTED AS |
| | STAND-ALONE UNITS OR QUALIFIED BY ENGINEERING SHALL USE |
| | PERFORMANCE CRITERIA CITED IN SECTIONS 1714.5.5.2, |
| | 1714.5.5.3 AND 1714.5.5.4. MULLIONS QUALIFIED BY AN |
| | ACTUAL TEST OF AN ENTIRE ASSEMBLY SHALL COMPLY WITH |
| | SECTION 1714.5.5.4, EXCEPT THAT MULLIONS IN ASSEMBLIES |
| | REQUIRING A DEFLECTION LIMITATION, AS DEFINED IN |
| | AAMA/WDMA/CSA 101/I.S.2/A440, SHALL MEET SECTIONS |
| | 1714.5.5.2 AND 1714.5.5.3. PRODUCTS NOT INCLUDED WITHIN |
| | THE SCOPE OF SECTION 1714.5.5.1 SHALL COMPLY WITH |
| | SECTIONS 1714.5.5.3 AND 1714.5.5.4. |
| | |
| | 1714.5.5.2 LOAD TRANSFER. MULLIONS SHALL BE DESIGNED TO |
| | TRANSFER THE DESIGN PRESSURE LOADS APPLIED BY THE |
| | WINDOW AND DOOR ASSEMBLIES TO THE ROUGH OPENING |
| | SUBSTRATE. |
| | |
| | 15B) ROOF TILE 2 ROOF TILE PRODUCT APPROVALS WERE |
| | SUBMITTED. ONLY ONE CAN BE SUBMITTED SINCE ONLY ONE CAN |
| | BE INSTALLED ON THE PROJECT. PLEASE ALSO CIRCLE THE |
| | TYPE OF ATTACHMENT SO THE MOMMENT OF UPLIFT FORTHE |
| | FASTENER CAN BE VERIFIED. |
| | |
| | 15C) ROOF FLAT DECK, NO PRODUCT APPROVAL WAS SUBMITTED |
| | FORTHIS PROJECT. PLEASE IDENTIFY WHICH SUB-SYSTEM WILL |
| | BE INSTALLED ON THIS BUILDING. PLEASE NOTE THAT THE |
| | TYPE OF INSULATION TO BE INSTALLED WILL ALSO HAVE TO |
| | MEET THE REQUIREMENTS OF THE ENERGY CODE AND INPUT DATA |
| | REPORT OF 30.3. |
| | |
| | 15D) EXTERIOR METAL DOOR, NO PRODUCT APPROVAL WAS |
| | SUBMITTED FOR THE D2 TYPE DOOR. 106.3 PRODUCT APPROVALS |
| | SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT |
| | APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE |
| | WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A |
| | COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE |
| | APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 16) THE ENERGY INPUT DATA REPORT FOR FLOOR SYSTEMS A |
| | 5.73 R-VALUE ALSO WAS TAKEN FOR FLOORING WITH CARPET |
| | AND RUBBER PADDING. PLEASE PROVIDE FLOOR FINISHES |
| | WITHIN THE PLANS SO THE INPUT DATA REPORT CAN BE |
| | VERIFIED. CARPET AND PADDING TO BE IN THE CONVENIENCE |
| | STORE? |
| | |
| | 17) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |