| 2009-07-09 17:02:33 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE PROVIDE SELECTIVE COORDINATION STUDY |
| | FOR 700 AND 701 SYSTEMS. PLEASE SEE 701.27, 701.18 AND |
| | 240.12. NFPA-110 6.5.1 |
| | |
| | 2) NOTE: PLEASE PROVIDE ELEVATION FOR EPS EQUIPMENT |
| | MEETING THE 100 YR STORM ELEVATIONS OR LEVELS ON THE |
| | SLOSH CHARTS FOR AREA. |
| | PLEASE SEE NFPA-110 7.2.3 |
| | |
| | 3) NOTE: PLEASE SEE 7.2.2 AND 7.2.1. LOCATIONS OF |
| | EQUIPMENT CLEARANCES OF ATS EQUIPMENT TWICE THE |
| | MINIMUMS PER 110.26 OF NFPA-70. |
| | |
| | 4) NOTE: PLEASE KNOW THAT NO MORE THAN 8FT OF |
| | UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE THE |
| | BUILDING. PLEASE SEE 230.70, 230.6 FOR WHAT IS |
| | CONSIDERED OUTSIDE THE BUILDING. |
| | |
| | 5) NOTE: IT IS UNCLEAR OF THE INTENT OF SERVICE RISER. |
| | IT APPEARS THE EXISTING 2000AMP SERVICE WILL BE TAPPED |
| | AND FED FROM NEW 400AMP SERVICE. THE LOADS SHOWN PER |
| | 220.87 ARE INDICATED HOWEVER THE MINIMUM SERVICE SIZE |
| | FOR BUILDING IS STILL REQUIRED TO BE SIZED PER MINIMUM |
| | LOAD CALCULATIONS. |
| | THIS IS BASED ON DETERMINING EXISTING LOADS. |
| | THE REMAINDER OF 220 WOULD APPLY FOR MINIMUM SERVICE |
| | SIZE. |
| | |
| | ** IF THIS IS NOT THE INTENT THEN PLEASE CALL TO GO |
| | OVER. BASED ON THE RISER IT APPEARS THE LINE SIDE OF |
| | GUTTER WHICH IS FED FROM THE EXISTING 2000AMP MAIN WILL |
| | BECOME NEW SERVICE FEEDERS. |
| | |
| | *** PLEASE BE AWARE OF OTHER COMMENTS FROM OTHER TRADES |
| | WHICH WILL AFFECT PLANS. |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |