| 2009-06-18 13:41:12 | |
| | ** DENIED PLANS * |
| | |
| | 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE |
| | FOLLOWING MINIMUM CODES. |
| | PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL |
| | PLANS. |
| | 2007 FBC W/ 2009 AMENDMENTS. |
| | 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE) |
| | 2002 NFPA-72 (OK) |
| | 2006 NFPA-1 |
| | 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN |
| | ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE |
| | THE 2008 NEC. |
| | |
| | PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 |
| | |
| | ** PLEASE BE AWARE FRONT COVER SHEET IS SHOWING 2007 |
| | AND 2004 FBC. REDLINED OFF THE 2004 |
| | |
| | 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR |
| | LIGHTING PERFORMANCE CALCULATIONS. THE SECTION WHICH |
| | USED TO ALLOW TRADE OFFS FOR OTHER AREAS IS NO LONGER |
| | IN THE CODE. THE ALLOWANCE FOR SCONCES, CHANDELIERS ETC |
| | ARE ALSO NOT IN THE CODE. |
| | PLANS SHOW CALCULATIONS FOR MOST AREAS HOWEVER SOME ARE |
| | IN QUESTION. |
| | FOR EXAMPLE: ROOM 604 NOT FIGURED INTO THE |
| | CALCULATIONS. |
| | |
| | |
| | 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS, |
| | AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3. |
| | THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR |
| | INFORMATION ON SYMBOL LEGEND. |
| | |
| | 4) NOTE: PLEASE CLARIFY WHY PANEL 6-OHP IS SHOWN. |
| | CIRCUITS ARE NOT SPECIFIC TO ANY ROOMS OR AREA LIGHTS |
| | FOR THE PLANS SHOWN. CIRCUITING NOT ON PLANS. |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | NEC 408.4 ,240, 220 |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |