Plan Review Notes
Plan Review Notes For Permit 09060140
Permit Number 09060140
Review Stop E
Sequence Number 3
Notes
Date Text
2009-07-28 19:04:49PROVISO/ BEFORE ROUGH
  
  
 1) NOTED FOR INFORMATION: 2HR WALL RATING AROUND ROOM
 1504 WITH A G TYPE DOOR WHICH IS STATED 45MIN/1HR DOOR
 ON DOOR SCHEDULE. IF THE INTENT BASED ON ELECTRICAL
 PLANS IS TO HAVE ROOM BE CONSIDERED AN IT ROOM MEETING
 DEFINITIONS OF 645.4 (1.5) AND NFPA-75 THIS MAY BE AN
 ITEM TO BE REVISED. THIS IS NOT A COMMENT TO CORRECT
 ARCHITECTURAL PLANS AS REVIEW HAS ALREADY BEEN PASSED
 BY THE BUILDING REVIEWER.
  
 2) NOTE: THE EFFECTIVE WATTAGE CAN NOT BE LESS THAN
 DESIGN/ PER 13-415.AB.5 DISPLAY AND ACCENT LIGHTING IS
 NO LONGER EXEMPT. THE FACT THE EFFECTIVE IS SHOWN LESS
 IS THE DIFFERENCE WATTAGE ON DISPLAY AND ACCENT
 LIGHTING. THE DESIGN IS STILL LESS THAN ALLOWANCE.
 CHECK PROGRAM AS THERE WAS A GLITCH UPDATE.
 UPDATE CALCULATIONS
  
 3) NOTE: LIGHTING CONTROLS FOR ACCENT LIGHTING IN
 LOCATIONS SUCH AS ROOM 1532 AND 1533 ARE NOT CLEAR.
 NOTES ON PLANS MENTIONS TO SEE DETAIL ON TC-1 ON SHEET
 E0.1 HOWEVER THE TC-1 DETAIL ON SAID NOTED SHEET DOES
 NOT MENTION ANY CONTROL FOR 1533 ONLY 1532.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717