| Plan Review Notes For Permit 09060140 |
| Permit Number |
09060140 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2009-07-28 19:04:49 | PROVISO/ BEFORE ROUGH | | | | | | | | | 1) NOTED FOR INFORMATION: 2HR WALL RATING AROUND ROOM | | | 1504 WITH A G TYPE DOOR WHICH IS STATED 45MIN/1HR DOOR | | | ON DOOR SCHEDULE. IF THE INTENT BASED ON ELECTRICAL | | | PLANS IS TO HAVE ROOM BE CONSIDERED AN IT ROOM MEETING | | | DEFINITIONS OF 645.4 (1.5) AND NFPA-75 THIS MAY BE AN | | | ITEM TO BE REVISED. THIS IS NOT A COMMENT TO CORRECT | | | ARCHITECTURAL PLANS AS REVIEW HAS ALREADY BEEN PASSED | | | BY THE BUILDING REVIEWER. | | | | | | 2) NOTE: THE EFFECTIVE WATTAGE CAN NOT BE LESS THAN | | | DESIGN/ PER 13-415.AB.5 DISPLAY AND ACCENT LIGHTING IS | | | NO LONGER EXEMPT. THE FACT THE EFFECTIVE IS SHOWN LESS | | | IS THE DIFFERENCE WATTAGE ON DISPLAY AND ACCENT | | | LIGHTING. THE DESIGN IS STILL LESS THAN ALLOWANCE. | | | CHECK PROGRAM AS THERE WAS A GLITCH UPDATE. | | | UPDATE CALCULATIONS | | | | | | 3) NOTE: LIGHTING CONTROLS FOR ACCENT LIGHTING IN | | | LOCATIONS SUCH AS ROOM 1532 AND 1533 ARE NOT CLEAR. | | | NOTES ON PLANS MENTIONS TO SEE DETAIL ON TC-1 ON SHEET | | | E0.1 HOWEVER THE TC-1 DETAIL ON SAID NOTED SHEET DOES | | | NOT MENTION ANY CONTROL FOR 1533 ONLY 1532. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|