Plan Review Notes For Permit 09060140
Permit Number 09060140
Review Stop E
Sequence Number 2
Notes
Date Text
2009-07-24 21:34:09 
 ** DENIED 2ND REVIEW. **
  
 1) NOTE: ONE SET OF MEP PLANS ARE NOT SIGNED, DATED OR
 SEALED AS REQUIRED UNDER FLORIDA STATUTES 471.025 AND
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002. THE FAC IS
 SPECIFIC WHICH REQUIRES *ALL* COPIES INCLUDING SETS OF
 PLANS AND DOCUMENTS FOR OWNER AND OWNER REPRESENTATIVE
 TO CONTAIN THE SIGNATURE, DATE AND SEAL. THE EXACT
 WORDING HAS BEEN EXTRACTED FROM THE SECTION NOTED
 ABOVE. THIS IS ONLY PART OF THE ENTIRE SECTION AS NOTED
 WHICH CAN BE EASILY VIEWED ONLINE AT THE FOLLOWING
 ADDRESS.
 HTTPS://WWW.FLRULES.ORG/GATEWAY/RULENO.ASP?ID=61G15-23.
 002
  
 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN BY HAND THE
 LICENSEE???S HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT
 ACCEPTABLE) AND AFFIX THE LICENSEE???S SEAL:
 (A) TO ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS,
 REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD; AND
 (B) TO ALL FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER???S REPRESENTATIVE;
  
  
 ** IF THIS WAS THE ONLY COMMENT ENGINEERS OF RECORD
 COULD MAKE TRIP TO OFFICE TO ADDRESS THE ABOVE.
  
 2) NOTE: NOTED FOR INFORMATION: 2HR WALL RATING AROUND
 ROOM 1504 WITH A G TYPE DOOR WHICH IS STATED 45MIN/1HR
 DOOR ON DOOR SCHEDULE. IF THE INTENT BASED ON
 ELECTRICAL PLANS IS TO HAVE ROOM BE CONSIDERED AN IT
 ROOM MEETING DEFINITIONS OF 645.4 (1.5) AND NFPA-75
 THIS MAY BE AN ITEM TO BE REVISED. THIS IS NOT A
 COMMENT TO CORRECT ARCHITECTURAL PLANS AS REVIEW HAS
 ALREADY BEEN PASSED BY THE BUILDING REVIEWER.
  
 3) NOTE: THE EFFECTIVE WATTAGE CAN NOT BE LESS THAN
 DESIGN/ PER 13-415.AB.5 DISPLAY AND ACCENT LIGHTING IS
 NO LONGER EXEMPT. THE FACT THE EFFECTIVE IS SHOWN LESS
 IS THE DIFFERENCE WATTAGE ON DISPLAY AND ACCENT
 LIGHTING. THE DESIGN IS STILL LESS THAN ALLOWANCE.
 CHECK PROGRAM AS THERE WAS A GLITCH UPDATE.
  
 4) NOTE: LIGHTING CONTROLS FOR ACCENT LIGHTING IN
 LOCATIONS SUCH AS ROOM 1532 AND 1533 ARE NOT CLEAR.
 NOTES ON PLANS MENTIONS TO SEE DETAIL ON TC-1 ON SHEET
 E0.1 HOWEVER THE TC-1 DETAIL ON SAID NOTED SHEET DOES
 NOT MENTION ANY CONTROL FOR 1533 ONLY 1532.
  
 ** WITH THE COMMENTS ABOVE NOTE #1 MUST BE ADDRESSED AT
 THIS TIME. OTHER ITEMS COULD BE DONE AS A PROVISO TO BE
 ADDRESSED WITH ANY OTHER REVISIONS BEFORE ROUGH
 ELECTRICAL INSPECTION.
  
 PLEASE CALL TO SET UP A TIME FOR ENGINEERS OF RECORD TO
 COME INTO OFFICE TO SIGN, DATE AND SEAL SAID PLANS SO
 THERE IS NO FURTHER DELAY OF PROJECT.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717