2009-06-17 09:39:22REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. FIRE RATED SEPARATION IS REQUIRED BETWEEN TENANT
 SPACE AND BUILDING COMMON AREAS (PLEASE SEE BUILDING
 PLAN REVIEW COMMENT #4 FOR ADDITIONAL INFORMATION).
 THERE ARE SEVERAL DUCT PENETRATIONS IN WALLS WHERE
 RATED TENANT SEPARATION WILL BE REQUIRED. PLEASE
 COORDINATE WITH THE ARCHITECT IN DETERMINING THE
 LOCATION OF THESE RATED WALL ASSEMBLIES AND SHOW THAT
 ALL DUCT PENETRATIONS OF THESE WALLS ARE PROTECTED IN
 ACCORDANCE WITH FBC-M 607.5.
  
 2. THE SUPPLY DROP SERVING "BOOKS" ROOM 1543 IS MISSING
 VOLUME DAMPER. VOLUME DAMPERS OR OTHER MEANS OF SUPPLY
 AIR ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DUCTS OR
 AT EACH INDIVIDUAL DUCT REGISTER, GRILLE OR DIFFUSER IN
 ACCORDANCE WITH FBC-M 603.17.
  