| 2009-07-08 10:26:32 | *****DENIED***** |
| | |
| | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 |
| | EDITION. |
| | |
| | 2. EFFECTIVE 12/31/2008, THE 2006 EDITION OF NFPA 101 |
| | IS TO BE REFERENCED. AMEND ON SHEET A0.1 IN THE |
| | BUILDING CODE ANALYSIS - FIRE SECTION. |
| | |
| | 3. ON SHEET A0.1, IT IS STATED IN THE BUILDING CODE |
| | ANALYSIS - OCCUPANT LOAD SECTION - THAT FIVE (5) EXITS |
| | ARE PROVIDED. INDICATE/SHOW THE PROVIDED EXITS. |
| | |
| | 4. AS PER NFPA 101 - LIFE SAFETY CODE - 2006 EDITION, |
| | CHAPTER 38 (NOT 36 AS LISTED ON SHEET A0.1 IN THE |
| | BUILDING CODE ANALYSIS - FIRE SECTION) IS THE REFERENCE |
| | FOR NEW BUSINESS OCCUPANCY. |
| | |
| | 5. IF APPLICABLE, ADD TO DOOR HARDWARE SCHEDULE NOTES |
| | (SHEET A2.2) THAT: DELAYED-EGRESS LOCKING COMPLYING |
| | WITH 7.2.1.6.1 AND ACCESS-CONTROLLED EGRESS DOORS |
| | COMPLYING WITH 7.2.1.6.2 OF NFPA 101 SHALL BE |
| | PERMITTED. |
| | |
| | 6. THE 2002 EDITION OF NFPA 72 (NATIONAL FIRE ALARM |
| | CODE) SHALL BE REFERENCED. |
| | |
| | 7. ON SHEET FA0.1, AMEND FIRE ALARM NOTE #17 TO REFLECT |
| | THAT: DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL |
| | FIRE ALARM. |
| | |
| | 8. ON SHEET FS0.1, AMEND GENERAL NOTE #1 TO REFLECT |
| | 2007 FLORIDA BUILDING CODE AND NFPA 13 - 2002 EDITION. |
| | AMEND NOTE #11 TO THE 2002 EDITION OF NFPA 13 (CURRENT |
| | ADOPTION BY THIS AHJ). |
| | |
| | 9.ON SHEET FS2.1, AMEND REMOTE AREA TO REFLECT NFPA 13 |
| | - 2002 EDITION. |
| | |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | SHEET INDICATING WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |