Plan Review Notes
Plan Review Notes For Permit 09060140
Permit Number 09060140
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-07-08 10:26:32*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. EFFECTIVE 12/31/2008, THE 2006 EDITION OF NFPA 101
 IS TO BE REFERENCED. AMEND ON SHEET A0.1 IN THE
 BUILDING CODE ANALYSIS - FIRE SECTION.
  
 3. ON SHEET A0.1, IT IS STATED IN THE BUILDING CODE
 ANALYSIS - OCCUPANT LOAD SECTION - THAT FIVE (5) EXITS
 ARE PROVIDED. INDICATE/SHOW THE PROVIDED EXITS.
  
 4. AS PER NFPA 101 - LIFE SAFETY CODE - 2006 EDITION,
 CHAPTER 38 (NOT 36 AS LISTED ON SHEET A0.1 IN THE
 BUILDING CODE ANALYSIS - FIRE SECTION) IS THE REFERENCE
 FOR NEW BUSINESS OCCUPANCY.
  
 5. IF APPLICABLE, ADD TO DOOR HARDWARE SCHEDULE NOTES
 (SHEET A2.2) THAT: DELAYED-EGRESS LOCKING COMPLYING
 WITH 7.2.1.6.1 AND ACCESS-CONTROLLED EGRESS DOORS
 COMPLYING WITH 7.2.1.6.2 OF NFPA 101 SHALL BE
 PERMITTED.
  
 6. THE 2002 EDITION OF NFPA 72 (NATIONAL FIRE ALARM
 CODE) SHALL BE REFERENCED.
  
 7. ON SHEET FA0.1, AMEND FIRE ALARM NOTE #17 TO REFLECT
 THAT: DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM.
  
 8. ON SHEET FS0.1, AMEND GENERAL NOTE #1 TO REFLECT
 2007 FLORIDA BUILDING CODE AND NFPA 13 - 2002 EDITION.
 AMEND NOTE #11 TO THE 2002 EDITION OF NFPA 13 (CURRENT
 ADOPTION BY THIS AHJ).
  
 9.ON SHEET FS2.1, AMEND REMOTE AREA TO REFLECT NFPA 13
 - 2002 EDITION.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722