Plan Review Notes
Plan Review Notes For Permit 09060140
Permit Number 09060140
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-04 17:14:03 
  
 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLANS SUBMITTED AFTER MARCH 1ST 2009 AND
 ADOPTION OF FAC SECTIONS 69A-69.004 AND 69A-3.012
 ADOPTED DECEMBER 31ST 2008 SHALL FALL UNDER THE
 FOLLOWING DESIGNS.
 SOME CODE ON COVER SHEET FOR EXAMPLE ARE OK, HOWEVER
 ONE SUCH CODE NOTED IS A 2008 NFPA-101.
 THIS SHOULD BE THE 2006 NFPA-101 WHICH WAS ADOPTED
 DECEMBER 31ST, 2008 BY FAC SECTIONS GIVEN ABOVE.
 THE COVER SHEET ON THE ELECTRICAL PLANS STATE THE 2008
 NFPA-70. AT THIS TIME THE STATE OF FLORIDA HAS NOT YET
 ADOPTED THE 2008 EDITION.
 PLEASE BE SURE THE THIS IS ADOPTED TO THE 2005 EDITION
 OF NFPA-70
  
 2) NOTE: ARCHITECTURAL TITLE BLOCK NEEDS TO CONTAIN ALL
 INFORMATION AS REQUIRED PER FAC 61G1-16.004 AND FS
 481.219.
 PLEASE KNOW THAT ANY SHEETS WHICH CONTAIN THE
 INFORMATION OF THE ARCHITECTURAL FIRM MUST CONTAIN THIS
 INFORMATION. PLEASE KNOW THAT ANY SHEETS WHICH DO NOT
 NEED TO BE REPRINTED MAY HAVE INFORMATION PLACED NEATLY
 ON DOCUMENTS. THIS WILL ALLEVIATE THE RE-PRINTING OF
 DOCUMENTS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 3) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.AB.5. THERE ARE AREAS IN WHICH
 THE DESIGN IS OVER THE ALLOWANCE.
 PLEASE ALSO SEE AREA 1532 WHICH IS NOTED AS *OPEN
 AREA*. AN OPEN AREA ALLOWANCE WOULD BE 1.1, PLANS STATE
 1.3. WOULD NOT THIS BE A CONFERENCE ROOM ALLOWANCE?
  
 4) NOTE: PLEASE ADJUST LIGHTING CONTROLS PER
 13-415.AB.1, .1.1, .1.2 AND .1.3.
 SEE NEW REVISIONS TO CHAPTER 13 AS THE ADOPTED 2009
 SUPPLEMENTS. THERE ARE SUBSTANTIAL CHANGES.
  
 EXAMPLE: DISPLAY OR ACCENT LIGHTING SEPARATE CONTROLS?
 PLEASE SEE ROOM 1532 WHICH INDICATE ACCENT LIGHTS ON
 THE TC CIRCUIT L13A-4 YET DOES NOT HAVE ANY OVER RIDE
 OR CONTROL IN THIS SEPARATE ROOM.
 EACH SEPARATE SPACE NEEDS CONTROLS.
  
 EXAMPLE: AREA 1533 ALSO HAS ACCENT LIGHTING ON THIS
 SAME CIRCUIT NOTED TO THE SAME TC. WHERE IS THE
 SEPARATE CONTROL DEVICE?
 OCCUPANT MUST SEE LIGHTING WHICH IS BEING CONTROLLED.
  
 EXAMPLE: PLEASE SEE 1542 WHICH INDICATES DEVICES FOR
 LIGHTING CONTROLS WHICH ARE NOT LOCATED ON THE SYMBOL
 LEGEND.
  
  
  
 ** THERE ARE REVISIONS TO CHAPTER 13 FOR LIGHTING
 CONTROLS.
  
 5) NOTE: PANELS L13A INDICATES FEED-THRU LUGS TO L13B.
 HOWEVER L13B DOES NOT INDICATE ANY FEED-THRU LUGS FOR
 L13C. RISER SHOWS THIS PANEL BEING FED FROM L13B.
 PLEASE SHOW HOW PANEL IS FED. IT IS ASSUMED PANEL B IS
 TO BE FEED THRU LUGS HOWEVER THIS CAN NOT BE ASSUMED.
 240.4,215.5, 310.16, GIVEN AS GENERAL SECTIONS FOR
 RISER COORDINATION.
 FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION OF
 PLANS.
  
 6) NOTE: PLEASE PROVIDE INFORMATION ON CLEARANCES OF
 EQUIPMENT. 110.26. THE TRANSFORMER SHOWN APPEARS TO
 ENCROACH ON PANEL H13A CLEARANCES. THE RISER OTHER
 INDICATES OTHER EQUIPMENT WHICH IS NOT SHOWN ON ROOM
 LAYOUT. IS THE TRANSFORMER FLOOR MOUNTED?
 PLEASE CHECK LAYOUT AND ADJUST.
  
 7) NOTE: PLEASE PLACE NOTED ON PLANS FOR ROOM 1504.
 THIS IS NOT AN IT ROOM PER NEC 645.4 1-5. WIRING
 METHODS IN NEC 645 ARE NOT PERMITTED. OR WORDS TO THAT
 AFFECT.
 IF WIRING METHODS OF NEC 645 ARE NEEDED OR IN REQUEST
 BY OWNERS IT STAFF, PLEASE KNOW THAT ALL ITEMS IN 1-5
 MUST BE MET.
 ANY OTHER CONSTRUCTION REQUIREMENTS SHALL BE
 NFPA-752003 EDITION AS ADOPTED PER FAC69A-3.012
  
 8) NOTE: NO ACCESS CONTROL SYSTEM IS PART OF THE
 SUBMITTED PLANS. ANY PROPOSED SYSTEM SHALL BE UNDER
 SEPARATE PERMITS AND PLANS.
 ** NFPA-101 2006 CHAPTER 7 DESIGN.
 ** J-BOXES MAY BE INSTALLED AS PART OF THE SCOPE SHOWN
 ON THIS PLAN.
  
 9) NOTE: LOW VOLTAGE FOR DATA/PHONE SHALL BE UNDER
 SEPARATE PERMIT. SCOPE OF WORK MAY BE REFERENCED ON
 PERMIT APPLICATION TO THIS MAIN SET OF PLANS FOR A TURN
 AROUND PERMIT. SEPARATE FEES ON LV PERMIT.
  
 10) NOTE: PLEASE KNOW THAT AT THIS TIME THE SCOPE OF
 WORK SHOWN ON PLANS FOR AREAS 1500, 1501, 1531, 1575,
 AND 1576 WILL BE HOLD FOR REVIEW AND SCOPE OF WORK
 UNDER THIS PERMIT APPLICATION.
 THIS IS COMMON AREA ELECTRICAL AND SPACE WHICH IS BEING
 SHOWN FED FROM THE TENANT SPACE ELECTRICAL SYSTEM. PER
 PLANS ANY FUTURE TENANT IN THE NW CORNER OF THE FLOOR
 WOULD ACTUALLY BE IN THIS TENANT SPACE TO ACCESS THEIR
 SPACE. WHERE IS TENANT SEPARATION?
 BUILDING ELECTRICAL ROOM IS ALSO SHOWN INSIDE THE
 TENANT SPACE. THIS IS NOT A NEW NOTE TO THIS BUILDING
 LOCATION ON SEVERAL DOCUMENTS ON PREVIOUS REVIEW.
 ACCESS, QUALIFIED PERSONNEL, ETC 24/7.
 THIS IS NOT AN ENTIRE TENANT OCCUPIED FLOOR. THERE IS
 OTHER TENANT SPACE SHOWN.
 AS NOTED ABOVE IN LIGHTING PERFORMANCE CALCULATION
 DESIGNS IN SOME AREAS ARE ABOVE ALLOWANCES BY SPACE BY
 SPACE.
  
 ** THERE ARE SEVERAL QUESTIONS ON DESIGN INTENT. PLEASE
 SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS. PLEASE KNOW THAT EVEN IF COMMENTS ARE
 NOT MADE BY OTHER TRADES COORDINATION OF ALL PLANS
 SHALL BE MET.
  
 11) NOTE: PLEASE SEE 250.30A3 AND 250.66 FOR THE SIZING
 OF THE GROUNDING ELECTRODE ON THE DERIVED SIDE OF THE
 TRANSFORMER. RISER NOTES A #6, YET THE DERIVED
 CONDUCTORS ARE 600MCM. SEE 250.66.
  
  
 12) NOTE: PLEASE KNOW THAT THE LIGHTING LISTED IN H
 PANEL WILL BE REQUIRED TO NOTED TO AREAS AND LOCATIONS
 MORE THAN SHOWN. THIS CAN BE A PROVISO ITEM.
 408.4.
  
  
 13) NOTE: ALL STROBE/HORN STROBE DEVICES ON FA0.1 ARE
 SHOWN AT 110 CD, YET SHEET FA2.1 DOES INDICATE SEVERAL
 AT 75CD. PLEASE COORDINATE.
 11-4.28.1,.2 AND.3. FOR LOCATION/HEIGHTS/LEVELS.
 FBC 106.1.1, 106.1.2, 106.5 FOR CLARITY, COORDINATION
 OF RECORD PLANS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  