Plan Review Notes
Plan Review Notes For Permit 09060140
Permit Number 09060140
Review Stop B
Sequence Number 1
Notes
Date Text
2009-06-15 18:02:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FBC1004, OCCUPANT LOAD NOT TO BE LESS THAN FBC TABLE
 1004.1.1; THEREFORE, PLEASE ROUND UP WHEN CALCULATING
 OCCUPANT LOAD (185 OCCUPANTS RATHER THAN 184).
  
 2. DESIGN INTENT REGARDING FIRE RATED WALLS IS NOT
 CLEAR (SEE OTHER COMMENTS FOR EXAMPLES). TO AVOID FIELD
 AND PLAN REVIEW ISSUES, PLEASE NOTE ALL FIRE RATED
 WALLS CONSISTENTLY ON THE PLAN. FOR INSTANCE, A0.1
 SHOWS ONLY TWO AREAS WITH RATED WALLS; THE AREA N.I.C.
 AND THE AREA ADJACENT TO ROOM 1560. THE WALL AT ROOM
 1560 IS SHOWN AS PARTIALLY RATED, NOT CONTINUOUS (SEE
 THE WALL BETWEEN COUNTER AND HALL).
  
 3. ELEVATOR LOBBY REQUIRED IN ACCORDANCE WITH
 FBC707.14.1, OR NOTE EXCEPTION TO THE REQUIRED ELEVATOR
 LOBBY ON THE PLAN. ALTHOUGH THE ELEVATOR AREA IS NOTED
 AS AN ELEVATOR LOBBY, THIS AREA IS OPEN TO OTHER AREAS,
 AND AN OCCUPANT IS FORCED TO GO THROUGH THIS AREA TO
 ACCESS THE EXIT.
  
 4. FBC708.1(7), TENANT SEPARATION REQUIRED BETWEEN THE
 TENANT SPACES AND THE COMMON AREA (TENANCY IN COMMON),
 PER BUILDING OFFICIAL. PLEASE CLEARLY NOTE EACH
 SEPARATE TENANT AREA; IT IS NOT CLEAR WHETHER ONE
 TENANT IS INCLUDED IN THIS PERMIT OR TWO (DUE TO A FIRE
 RATED WALL BETWEEN TWO AREAS). PLEASE REVISE WALL
 CONSTRUCTION TO INCLUDE 1 HOUR WALLS WHERE REQUIRED.
  
 5. OPENING PROTECTION REQUIRED (3/4 HOUR) FOR ALL
 OPENINGS IN TENANT SEPARATION WALLS, FBC TABLE 715.4.
  
 6. A0.1 STATES THERE ARE 5 EXITS; PLEASE SEE DEFINITION
 OF EXIT, FBC1002. IT APPEARS THAT THERE ARE TWO EXITS;
 PLEASE REVISE.
  
 7. A0.1, SITE LOCATION OR GENERAL NOTES, ITEM 10, NOC
 IS TO BE POSTED ON JOB AT ALL TIMES; LANGUAGE IN THIS
 NOTE IS INCORRECT. PLEASE EITHER REVISE NOTE TO COMPLY
 WITH FS713.13 OR REMOVE THE NOTE.
  
 8. PROVIDE A HEAD OF WALL ASSEMBLY (HW) FOR THE TOP OF
 THE RATED PARTITION WALL, FBC708.4.
  
 9. THE ARCHITECT'S SEAL IS TO INCLUDE A DATE, FS481.
  
 10. SHOW REQUIRED KNEE SPACE FOR SINK, A4.2,
 FBC11-4.24.
  
 11. SHOW HOW DOOR F COMPLIES WITH FBC1003.6, MEANS OF
 EGRESS CONTINUITY.
  
  