| 2009-07-04 09:56:39 | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | ** PLANS WERE STAMPED BY ELECTRICAL AND COMMENTS |
| | REDLINED HOWEVER HAVE BEEN VOIDED BASED ON BUILDING |
| | REVIEW COMMENTS. THE SHEET WHICH ELECTRICAL IS SHOWN |
| | WILL NEED TO BE UPDATED. PLEASE ADDRESS THE OTHER MINOR |
| | ELECTRICAL COMMENTS BELOW AT THE SAME TIME. |
| | |
| | 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER |
| | ADOPTION BY THE STATE OF FLORIDA. |
| | |
| | ELECTRICAL SHALL CONTAIN: |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | |
| | PLEASE SEE FAC 69A-60.004 AND 69A-3.012. |
| | FS 553.73 AND 2007 FBC WITH 2009 SUPPLEMENTS |
| | |
| | 2) NOTE: THE SCOPE SHOWN INCLUDES ENCLOSING AREA TO BE |
| | PART OF A HABITABLE ROOM. PLEASE SEE 210.52 AS |
| | RECEPTACLES SPACING SHALL MEET REQUIRED SPACING WITHIN |
| | 6FT OF A DOOR. THE FIXED GLASS PANELS ARE COUNTED AS |
| | WALL SPACE THEREFORE REQUIRING THE RECEPTACLE TO BE |
| | WITHIN 6FT OF DOOR OPENING. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |