| 2009-10-26 10:07:57 | BUILDING PROVISO: |
| | |
| | 1) SKWTCH SK-2 THE FRAME WALL DOES NOT INDICATE IF THIS |
| | IS INTERIOR OR |
| | EXTERIOR, IF CONSIDERED EXTERIOR COMPLY WITH: |
| | |
| | 2304.11.2.6 WOOD SIDING. CLEARANCE BETWEEN WOOD SIDING |
| | AND EARTH |
| | ON THE EXTERIOR OF A BUILDING SHALL NOT BE LESS THAN 6 |
| | INCHES (152 MM) |
| | EXCEPT WHERE SIDING, SHEATHING AND WALL FRAMING ARE OF |
| | NATURALLY DURABLE |
| | OR PRESERVATIVE-TREATED WOOD. |
| | |
| | 2) NO ROOFING PERMIT HAS BEEN APPLIED FOR AT THIS TIME |
| | (10-26-09) |
| | FL S S 489.13 QUALIFICATIONS FOR PRACTICE; RESTRICTIONS |
| | (2) (B) A GENERAL, BUILDING ,OR RESIDENTIAL CONTRACTOR |
| | SHALL NOT BE REQUIRED TO SUBCONTRACT THE INSTALLATION, |
| | OR REPAIR MADE UNDER WARRANTY, OF WOOD SHINGLES, WOOD |
| | SHAKES, OR ASPHALT OR FIBERGLASS SHINGLE ROOFING |
| | MATERIALS ON A NEW BUILDING OF HIS CONSTRUCTION. |
| | (G) NO GENERAL, BUILDING OR RESIDENTIAL CONTRACTOR |
| | CERTIFIED AFTER 1973 SHALL ACT AS, HOLD HIMSELF OUT TO |
| | BE, OR ADVERTISE HIMSELF TO BE A ROOFING CONTRACTOR |
| | UNLESS HE IS CERTIFIED OR REGISTERED AS A ROOFING |
| | CONTRACTOR. |
| | |
| | THE FLAT ROOF AND ASSOCIATED NOA'S WILL REQUIRE EITHER |
| | A REGISTER OR CERTIFIED ROOFING CONTRACTOR TO APPLY AND |
| | RECEIVE A ROOFING PERMIT. |
| | |
| | THE NOA SUBMITTED WITH ENHANCED FASTENING REVIEWED: |
| | NOA 09-0224.01 |
| | GAF CORP PAGES 29-30, SYSTEM TYPE:E2 |
| | DESIGN PRESSURE -60 PSF |
| | EXPOSURE : C |
| | ATLANTIC & CARIBBEAN ROOFING CONSULTING, LLC ENHANCED |
| | FASTENING P2=71.68 & P3 -101.2. |
| | |