Plan Review Notes
Plan Review Notes For Permit 09060129
Permit Number 09060129
Review Stop P
Sequence Number 1
Notes
Date Text
2009-07-01 13:19:04DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. SHT P1 THE WATER ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS ONLY COLD
 WATER TO THE MOP SINK AND THE HOSE BIBB LINE CONNECTING
 BY THE ICE MAKER. SECTION 106.1.1 PLEASE CORRELATE. --
 ALSO THE HOSE BIBB REQUIRES A SHUT OFF VALVE ON THE
 SUPPLY LINE TO THE HOSE BIBB. SECTION 606.2(2).
  
 2. SHT P1 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN FOR THE FLOOR DRAIN DOWNSTREAM OF THE MOP
 SINK. PLEASE CORRELATE. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  