| 2009-07-01 13:07:33 | DENIED |
| | REFERENCE: |
| | FBC-2007 FUEL GAS |
| | |
| | A. THE FOLLOWING INFORMATION IS REQURIED FOR THE |
| | SEPARATE GAS PERMIT: |
| | |
| | 1. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- PLANS SHOW 2 |
| | PSI AT METER BUT NOTES INDICATED SIZED PER .5 PSI |
| | TABLE. PLEASE CLARIFY. |
| | |
| | 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE |
| | SEC. G2413.2. -- SUBMIT MANUF SHEETS FOR NEW TANKLESS |
| | WATER HEATER. |
| | |
| | 3. PER SECTION 404.8 METALLIC PIPE EXPOSED TO CORROSIVE |
| | ACTION, SUCH AS SOIL CONDITION OR MOISTURE, SHALL BE |
| | PROTECTED IN AN APPROVED MANNER. GALVANIZED PIPE IS NOT |
| | ALLOWED UNDERGROUND UNLESS PER SECTION 404.8.2 THE PIPE |
| | PROTECTIVE COATINGS AND WRAPPINGS SHALL BE APPROVED FOR |
| | THE APPLICATION AND SHALL BE FACTORY APPLIED. PLEASE |
| | INDICATE METHOD OF PIPE PROTECTION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |