Plan Review Notes
Plan Review Notes For Permit 09060129
Permit Number 09060129
Review Stop G
Sequence Number 1
Notes
Date Text
2009-07-01 13:07:33DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQURIED FOR THE
 SEPARATE GAS PERMIT:
  
 1. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- PLANS SHOW 2
 PSI AT METER BUT NOTES INDICATED SIZED PER .5 PSI
 TABLE. PLEASE CLARIFY.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2. -- SUBMIT MANUF SHEETS FOR NEW TANKLESS
 WATER HEATER.
  
 3. PER SECTION 404.8 METALLIC PIPE EXPOSED TO CORROSIVE
 ACTION, SUCH AS SOIL CONDITION OR MOISTURE, SHALL BE
 PROTECTED IN AN APPROVED MANNER. GALVANIZED PIPE IS NOT
 ALLOWED UNDERGROUND UNLESS PER SECTION 404.8.2 THE PIPE
 PROTECTIVE COATINGS AND WRAPPINGS SHALL BE APPROVED FOR
 THE APPLICATION AND SHALL BE FACTORY APPLIED. PLEASE
 INDICATE METHOD OF PIPE PROTECTION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  