Plan Review Notes
Plan Review Notes For Permit 09060129
Permit Number 09060129
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-07-09 12:42:47*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. EFFECTIVE 12/31/2008, THE 2006 EDITION OF NFPA 101,
 LIFE SAFETY CODE, SHALL BE REFERENCED. AMEND REFERNCE
 TO THE 2003 EDITION AS LISTED ON A1.0 AND E1 SHEETS.
  
 3. ON THE EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE
 HIGHWAY, DISPLAY/SHOW THE BUILDING'S ADDRESS NUMBERS.
 AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE.
  
 4. SHOW THE LOCATION OF RATED FIRE EXTINGUISHER(S)
 WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 5. ON SHEET A1.0, ELIMINATE REFERENCE TO NFPA 72
 (NATIONAL FIRE ALARM CODE) IF BUILDING ISN'T EQUIPPED
 WITH A FIRE ALARM SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722