| 2009-06-30 17:02:11 | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS SHOWING MINIMUM DESIGNS |
| | AND INSTALLATIONS PER CODES WHICH ARE REQUIRED TO BE |
| | REFLECTED ON PLANS. |
| | THE INCORRECT CODES ARE STATED. PLANS INDICATE THE |
| | PREVIOUS 2004 FBC WHICH HAS NOT BEEN AN ADOPTED CODE |
| | SINCE MARCH 1ST, 2009. |
| | PLANS SHOULD REFLECT THE FOLLOWING CODES COORDINATION |
| | BETWEEN PLANS IS NEED. ELECTRICAL PLANS STATE DIFFERENT |
| | CODES FROM BUILDING. |
| | PLANS REFERENCE 2002 NFPA-72, WILL THERE BE ANY WORK |
| | PER THIS CODE? |
| | |
| | 2007 FBC WITH 2009 REVISIONS |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE FBC 13-415.AB.5 FOR MINIMUM |
| | LIGHTING PERFORMANCE CALCULATIONS. FIXTURES NEED TO BE |
| | COMPLETE AT THIS TIME. THESE MAY ALWAYS BE REVISED AT A |
| | LATER DATE. |
| | |
| | 3) NOTE: PLEASE SEE FBC 13-415.AB.1, .1.4 FOR EXTERIOR |
| | LIGHTING CONTROLS. |
| | |
| | 4) NOTE: PLEASE INDICATE SIGN CIRCUIT PER 600.5 |
| | |
| | 5) NOTE: PLEASE SEE NFPA-96 FOR ANY SHUT DOWN OF |
| | ELECTRICAL UNDER HOOD, NEW OR EXISTING? PANEL DOES NOT |
| | INDICATE ANY SHUNT TYPE BREAKERS. |
| | |
| | 6) NOTE: PLEASE INDICATE NEW OR EXISTING WP GFI FOR A/C |
| | EQUIPMENT LOCATIONS PER 210.63,210.8B3 |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |