| 2009-10-06 09:49:54 | PLANNING AND ZONING: **** FAILED- COMMENTS NOT |
| | ADDRESSED**** |
| | |
| | 1. RESPOND TO COMMENTS IN WRITING. RESPONSE TO |
| | RE-SUBMITTAL, LANDSCAPING REQUIREMENTS WERE NOT WAIVED. |
| | CONTACT ME TO DISCUSS COORDINATION OF PLANS FOR BOTH |
| | THIS GENERATOR PERMIT AND THE MAIN GENERATOR PERMIT |
| | (08060582) WITH FENCE PERMIT (09080160). ALL |
| | IMPROVEMENTS ARE REQUIRED TO BE SHOWN IN MINOR |
| | AMENDMENT PLANS. SEE COMMENT #2. |
| | |
| | 2. THIS PROPERTY IS PART OF THE IBIS RESIDENTIAL |
| | PLANNED DEVELOPMENT (" IBIS RPD"), AN APPLICATION FOR A |
| | MINOR AMENDMENT TO THE RPD SHOWING THE PROPOSED NEW |
| | LIFE-SAFETY GENERATOR AND NEW GAS TANK (LOCATED JUST |
| | WEST OF THE ENCLOSURE THAT HOUSES THE EXISTING APS AND |
| | TRANSFORMER) WILL BE REQUIRED TO BE FILED TO THE |
| | PLANNING AND ZONING DEPARTMENT AND APPROVED PRIOR TO |
| | THE BUILDING PERMIT BEING APPROVED. SEE |
| | HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER |
| | DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD |
| | AMENDMENT. |
| | |
| | THE COMMENTS BELOW REFLECT THE INFORMATION NEEDED ON |
| | SITE PLAN, PRIOR TO SUBMITTAL OF THE MINOR AMENDMENT TO |
| | THE IBIS RPD. |
| | |
| | 3. THE SITE PLAN SHALL INCLUDE THE FOLLOWING: |
| | |
| | A. PROVIDE ELEVATIONS WITH DIMENSIONS INCLUDING TOTAL |
| | HEIGHT OF GENERATOR AND TANK TO INCLUDE SLAB. PROVIDE A |
| | FLOOR PLAN OF SCREENING AND LANDSCAPING DETAIL. INCLUDE |
| | WALL/FENCE HEIGHT, ETC., |
| | B. PROVIDE SETBACK DISTANCE FROM PROPERTY LINE. |
| | |
| | NOTE: ADDITIONAL CURBING MAY BE REQUIRED TO CONTINUE |
| | WITH THE NEW CURBING THAT WAS ADDED FOR THE EXISTING |
| | TRANSFORMERS AND NEW 500KW GENERATOR. PROVIDE DETAIL OF |
| | ALL ENCLOSURES WITH LANDSCAPING ON THE SITE PLAN/FLOOR |
| | PLANS. |
| | |
| | 4. PURSUANT TO SECTION 94-444(B) OPEN SPACE |
| | STANDARDS: |
| | |
| | (B) FUEL OR OIL OR PROPANE TANKS, GENERATORS SHALL NOT |
| | BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED. |
| | SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE |
| | CONCRETE, OTHER |
| | DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND |
| | STEEL. |
| | |
| | WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES |
| | PLANTED AT TWO-FOOT INTERVALS. PROVIDE TYPE OF |
| | LANDSCAPING TO BE INSTALLED. A FOUR-SIDED ENCLOSURE |
| | WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN |
| | OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN |
| | APPROVAL. |
| | |
| | THE SCREENING SHALL ENCLOSE BOTH LIFE-SAFETY GENERATOR |
| | AND GAS TANK INCLUDING ROOFTOP EXHAUST. |
| | |
| | 5. PURSUANT TO SECTION 94-305(B)(4) SETBACKS (B)(4) |
| | SETBACK ENCROACHMENT: |
| | MECHANICAL EQUIPMENT SHALL NOT PROJECT MORE THAN 4 FEET |
| | INTO A SETBACK. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. |
| | |
| | LINDA MIA FRANCO |
| | SENIOR PLANNER |
| | PLANNING AND ZONING DEPARTMENT |
| | TEL: (561) 822-1443 |
| | EMAIL: [email protected] |
| | |