Plan Review Notes
Plan Review Notes For Permit 09060113
Permit Number 09060113
Review Stop E
Sequence Number 1
Notes
Date Text
2009-06-26 08:48:21 
 ** DENIED PLANS **
  
 *** STORES #50, 319, AND 651
  
 *** IT IS IMPORTANT TO KNOW THAT THERE IS INFORMATION
 NOT YET SHOWN OR SUBMITTED FOR REVIEW OF MINIMUM CODE
 COMPLIANCE. THEREFORE THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
 1) NOTE: PLEASE KNOW THE VALUE FOR THE COMPLETE SCOPE
 OF WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT
 WHICH IS PERMANENTLY INSTALLED AND DESIGN COST. EVEN IF
 ANY OF THESE ARE OWNER SUPPLIED. THE VALUE SUBMITTED IS
 LOW FOR THE COMPLETE SCOPE OF WORK AS SHOWN.
 THE VALUE ON THE BASE BUILDING/REMODEL SCOPE OF WORK
 WAS NOT ADJUSTED EVEN THOUGH THE SCOPE OF WORK WAS
 SUBSTANTIALLY INCREASED.
 FBC 108.3
  
 2) NOTE: PLEASE SEE THE COVER SHEET FOR THE SUBMITTED
 PROJECT WHICH PROVIDES A LIST OF ALL SHEETS SUBMITTED.
 THE E-1, ELECTRICAL RISER SHEET IS CLEARLY STATED
 HOWEVER NO E-1 SHEET WAS SUBMITTED. THIS WAS GONE OVER
 SPECIFICALLY IN PREVIOUS MEETINGS THAT EACH PERMITTED
 SCOPE OF WORK SET OF PLANS NEEDS TO CONTAIN THE MINIMUM
 SHEETS FOR RECORD PLANS.
 PLEASE BE SURE THE FOLLOWING CODES ARE REFLECTED ON
 PLANS. THE ONLY SHEET THAT HAS ANY CODE REFERENCES IS
 THE P SHEET.
 2005 NFPA-70
 2006 NFPA-101
 2002 NFPA-110
  
 3) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE MINIMUM
 RUN TIMES FOR EMERGENCY LIFE SAFETY SYSTEMS BACK UP PER
 NFPA-101 7.8, 7.9. THIS SHOULD BE A NOTE ON THE
 E-SHEETS FOR LIGHTING ALSO.
 PLUMBING SHEETS DO CONTAIN THE NOTE FOR THE 14HRS WHICH
 IS OK.
  
 4) NOTE: PLEASE BE SURE TO PROVIDE ELEVATION OF THE
 GENERATOR FOR ANY AREAS IN WHICH THE GENERATOR MAY BE
 LOCATED IN A FLOOD ZONE A. PLEASE SEE CHAPTER 7 OF
 NFPA-110 FOR LOCATIONS. PLEASE SEE 7.2.3 FOR HEIGHTS.
 NOT ALL STORE LOCATIONS ARE IN FLOOD ZONES. PLEASE BE
 SURE THE ELEVATION FOR 100YEAR STORM OR SLOSH CHARTS
 ARE INDICATED.
  
 5) NOTE: PLEASE SEE NFPA-110 7.11.4. LIGHTNING
 PROTECTION FOR UNITS EPS UNITS LOCATED OUTSIDE. THE
 ADOPTED APPLICABLE STANDARD IS NFPA-780, 2003.
  
 6) NOTE: PLEASE BE SURE TO INCLUDE CIRCUITS AND PANEL
 SCHEDULE FOR ITEMS SUCH AS ANY BLOCK HEATER, BATTERY
 CHARGER ETC.
 408.4, 240.4,310.16 ETC NEC. SECTION 7.12 OF NFPA-110.
  
 7) NOTE: PLEASE SEE SECTION 7.9 OF NFPA-110.
 PLEASE ALSO BE SURE TO SEE SECTION 7.9.3.1. THIS IS A
 COMMON ITEM IN WHICH INSPECTIONS AND/OR INSTALLATIONS
 ARE FAILED DUE TO CHANGES MADE. THE PLANS STATE THE
 BLACK STEEL, HOWEVER PLEASE BE SURE THIS IS NOT
 ADJUSTED IN FIELD.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  