2009-07-20 11:56:37PERMIT APPLICATION INDICATES "INSTALLING GENERATOR"
  
 1. PROPER LABELS OR SIGNS SHALL BE PROVIDED FOR THE NEW
 LP FUEL TANK. THESE SHALL INCLUDE PRODUCT NAME, NO
 SMOKING OR OPEN FLAMES.
  
 2. SUITABLE DEVICES SHALL BE PROVIDED TO PROTECT THE
 TANK FROM MECHANICAL DAMAGE.
  
 3. NO CODE REFERENCES PROVIDED ON THE DRAWINGS PREPARED
 BY PBS&J.
  
 4. WHAT SYSTEMS OR DEVICES WILL THE GENERATOR SUPPLY
 POWER TO AND FOR HOW LONG.
  
 5. ALL ELECTRICAL WORK SHALL COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
  
 MIKE CARSILLO, BATTALION CHIEF