| Plan Review Notes For Permit 09060112 |
| Permit Number |
09060112 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-20 11:56:37 | PERMIT APPLICATION INDICATES "INSTALLING GENERATOR" | | | | | | 1. PROPER LABELS OR SIGNS SHALL BE PROVIDED FOR THE NEW | | | LP FUEL TANK. THESE SHALL INCLUDE PRODUCT NAME, NO | | | SMOKING OR OPEN FLAMES. | | | | | | 2. SUITABLE DEVICES SHALL BE PROVIDED TO PROTECT THE | | | TANK FROM MECHANICAL DAMAGE. | | | | | | 3. NO CODE REFERENCES PROVIDED ON THE DRAWINGS PREPARED | | | BY PBS&J. | | | | | | 4. WHAT SYSTEMS OR DEVICES WILL THE GENERATOR SUPPLY | | | POWER TO AND FOR HOW LONG. | | | | | | 5. ALL ELECTRICAL WORK SHALL COMPLY WITH NFPA 70, THE | | | NATIONAL ELECTRICAL CODE. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|