| Plan Review Notes For Permit 09060097 |
| Permit Number |
09060097 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-09-30 13:48:02 | **PROVISOS** | | | 1. NEED PRODUCT APPROVAL FOR PRE-ENGINEERED STAND ON | | | SITE PRIOR TO INSPECTION. | | | 2. NEED PROTECTION OF DUCT PENETRATIONS FOR EF-1 AND | | | EF-3 DUCTS AT FLOOR OR SHAFT PENETRATIONS PER FBC-M | | | 607.5.5 OR 607.5.6. | | | 3. SUBMIT MANUFACTURER'S WIND RESISTANCE DATA FOR | | | ROOFTOP UNITS PER FBC-M 301.12. | | | 4. SUBMIT COOLING LOAD CALCULATIONS PER FBC-B | | | 13-407.AB.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|