| Date |
Text |
| 2009-06-29 09:20:28 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 11 |
| | FBC-2007 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS SIGNED & SEALED BY MICHAEL SIPULA. THE |
| | PRINTED NAME OF THE PERSON SEALING THE DOCUMENT IS |
| | REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC |
| | 61G1-16.004(6) & FS 481.2055. |
| | |
| | 2. SHT A.1 TOILET ROOM 5 SHALL BE ADAPTABLE. PLEASE |
| | INDICATE ON PLANS. SECTION 11-4.1.3(11). |
| | |
| | 3. SHT A.1 THE SINKS IN THE BREAK ROOM & THE CEO BAR |
| | SHALL BE ACCESSIBLE. SECTION 11-4.24. PLEASE SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH ALL SUBSECTIONS. |
| | |
| | 4. SHT A.1 SHOW THE CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET AND LAV IN THE ACCESSIBLE STALLS. THE LAV CAN |
| | NOT BE IN THE CLEAR FLOOR SPACE OF THE WATER CLOSET. |
| | SEE FIGURE 11-30E. |
| | |
| | 5. PLEASE SHOW COMPLIANCE FOR THE FOLLOWING: |
| | ___W/C'S |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4/16/5 FLUSH CONTROLS (SHT A.8 DETAILS C & D SHOW |
| | THE FLUSH CONTROLS ON THE WRONG SIDE). |
| | ___LAVS |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE (TR/1 & TR/2) |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | |
| | 6. SHT A.8 THE ACCESSIBLE STALL IN TR/2 2ND FLOOR |
| | LOBBY/TOILET AREA DOES NOT COMPLY WITH SECTION |
| | 11-4.17.3 OR FIGURE 30E. THE LAV CAN NOT BE IN THE 5FT |
| | WIDE CLEAR FLOOR SPACE. |
| | |
| | SHT A.8 PLEASE SHOW THE ACCESSIBLE W/C'S TO BE 18 |
| | INCHES OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. |
| | FIGURE 30E. LAVS TO BE MINIMUM 15 INCHES OFF THE WALL |
| | TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE |
| | 30 INCH DIMENSION OF THE CLEAR FLOOR SPACE. 11-4.19.3. |
| | |
| | 7. SHTS P1.01 & P2.01 FLOOR DRAINS ARE NOT APPROVED |
| | INDIRECT WASTE RECEPTORS. A FLOOR SINK OR HUB DRAIN IS |
| | REQUIRED. SECTIONS 802.3 & 802.3.2. |
| | |
| | |
| | 8. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING |
| | REQUIRED INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| | 2007 FUEL GAS CODE. - THE CORRESPONDING LENGHTS SHALL |
| | BE INDICATED TO VERIFY DISTANCE TO THE MOST REMOTE |
| | OUTLET. |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE |
| | SEC. G2413.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |