| Date |
Text |
| 2009-06-22 11:14:53 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PG M1.01 AND M1.02: FILE ROOMS APPEAR TO BE |
| | INCIDENTAL USE AREAS IN ACCORDANCE WITH FBC-B 508.2. IN |
| | FULLY SPRINKLERED BUILDINGS, THIS ROOM REQUIRES SMOKE |
| | PARTITIONS IN ACCORDANCE WITH 508.2.2.1. SHOW THE |
| | TRANSFER AIR OPENING TO BE PROTECTED WITH SMOKE DAMPER |
| | IN ACCORDANCE WITH FBC-710.7. NOTE: THIS CONDITION |
| | WOULD APPLY TO ALL INCIDENTAL USE AREAS. |
| | |
| | 2. PAGE M1.01: EXHAUST DUCTS FOR EF-3 MISSING SIZE. |
| | PROVIDE MISSING INFORMATION IN ACCORDANCE WITH FBC-M |
| | 501.1. |
| | |
| | 3. M1.01: FLOOR PLAN SHOWS EF-3 WITH 500 CFM WHILE |
| | EXHAUST GRILLS AND FAN SCHEDULE CALL FOR 400 CFM. |
| | PLEASE COORDINATE NOTES AND PLANS IN ACCORDANCE WITH |
| | FBC-M 501.1 AND FBC-B 106.1.1. |
| | |
| | 4. M1.01: RTU-2 AND RTU-3 SUPPLY RISERS SHOW DUCT SMOKE |
| | DETECTORS ON ONE BRANCH ONLY. THIS LEAVES THE OTHER |
| | BRANCH NOT COVERED BY DUCT SMOKE DETECTOR. THE |
| | DETECTORS SHALL BE LOCATED TO SAMPLE THE ENTIRE AIRFLOW |
| | IN ACCORDANCE WITH FBC-M 606.3. |
| | |
| | 5. M1.01: EF-1, EF-2 AND EF-3 ARE SHOWN WITH THE |
| | EXHAUST DUCT ON THE DISCHARGE SIDE OF THE FAN LOCATED |
| | IN THE RETURN AIR PLENUM CEILING. EXHAUST DUCTS UNDER |
| | POSITIVE PRESSURE SHALL NOT BE LOCATED IN A PLENUM IN |
| | ACCORDANCE WITH FBC-M 601.5. |
| | |
| | 6. M1.01: PROVIDE GRAVITY OPERATED OR MOTORIZED DAMPER |
| | ON EXHAUST DUCTS TO SHUT WHEN SPACES ARE NOT IN USE PER |
| | FBC-B 13-409.AB.3.3. |
| | |
| | 7. M2.01 CONTAINS MOUNTING DETAILS FOR RTUS, FANS AND |
| | CURBS. THESE DETAILS ARE IN CONFLICT WITH CURB/UNIT |
| | ATTACHMENT DETAILS ON PAGE S401. PLEASE COORDINATE |
| | PLANS AND DETAILS AND DEMONSTRATE COMPLIANCE WITH FBC-M |
| | 301.12. |
| | |
| | 8. M2.01: PLAN CONTAINS INSTALLATION DETAIL FOR FIRE |
| | DAMPERS. NO PARTICULAR BRAND/MAKE OF FIRE DAMPER IS |
| | SPECIFIED ON PLANS. FIRE DAMPERS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE MANUFACTURER???S INSTALLATION |
| | INSTRUCTIONS AND LISTING PER FBC-M 607.2. |
| | |
| | 9. PROVIDE MANUFACTURER???S DATA SHOWING ALL OUTDOOR |
| | APPLIANCES SUCH AS RTUS, EXHAUST FANS AND CONDENSING |
| | UNITS ARE DESIGNED FOR WIND RESISTANCE IN ACCORDANCE |
| | WITH FBC-M 301.12. SEE COMMENT ABOVE AS MANUFACTURERS |
| | INSTALLATION DATA FOR WIND RESISTANCE MAY BE IN |
| | CONFLICT WITH MECHANICAL AND STRUCTURAL DETAILS ON |
| | PLANS. |
| | |
| | 10. ME1.01: PLAN SHOWS CONDENSING UNITS INSTALLED ON |
| | ROOF STAND. NO DETAIL FOR THIS ROOF STAND COULD BE |
| | FOUND FOR THIS STAND. IS THIS A SITE BUILT OR |
| | PRE-ENGINEERED STAND? PROVIDE DETAIL FOR SITE BUILT |
| | STAND OR PRODUCT APPROVAL FOR PRE-ENGINEERED STAND, |
| | DEMONSTRATING COMPLIANCE WITH WIND RESISTANCE |
| | REQUIREMENTS OF FBC-M 301.12. |
| | |
| | 11. P1.01 SHOWS CONDENSATE PUMPS OUTSIDE THE BUILDING |
| | TO DISPOSE OF CONDENSATE FROM AC-1 AND AC-2. SHOW ON |
| | PLANS WHERE THESE PUMPS WILL DISCHARGE THE CONDENSATE |
| | PER FBC-M 307.2.1. ALSO, ELECTRICAL PLANS DO NOT SHOW |
| | ANY POWER FOR THE PUMPS AT THE PROPOSED LOCATIONS. |
| | PLEASE CLARIFY THE DESIGN INTENT FOR CONDENSATE |
| | DISPOSAL FOR THESE UNITS. |
| | |
| | 12. PROVIDE DETAIL SHOWING EXTERIOR BLOCK WALL FINISH |
| | ABOVE CEILING. NO SUCT DETAIL COULD BE FOUND IN |
| | ARCHITECTURAL PLANS. THIS IS A PLENUM SPACE. WALL SHALL |
| | BE INSULATED AND LINED WITH AN APPROVED AIR BARRIER IN |
| | ACCORDANCE WITH FBC-M 603.8. |
| | |